ESP MAGPRO16 Installation And Programming Manual page 36

Intelligent interactive analogue adressable fire alarm control panel
Table of Contents

Advertisement

MAGPRO16 Addressable Fire Alarm Panel – Installation and Programming Manual
MAGPRO-Mini – Mini input module
The MAGPRO-Mini is a compact module with one input. The module monitors and transfers to control panel the state
of this input - state ON or state OFF. MAGPRO-Mini is designed for built-in installation in the mounting box of the
device.
The activation of the MAGPRO-Mini input can be programmed according the application. To program the generated
event at the input, press button (1) IN 1 – in the submenu are active two fields for setting:
GENERATES – Use the up/ down arrow buttons to select generated event at the input: FIRE/ EVACUATE/
RESET/ MESSAGE ALARM/ MESSAGE FAULT/ MESSAGE WARNING/ SILENCE BUZZER/ SILENCE
ALARM / CLASS CHANGE*
DELAY – The field is common for all events. Enter time delay 0-600 sec for activation event.
(2) ON/ OFF LED – Press to switch on/ off the device LED.
* CLASS CHANGE - To use the class change function, connect the terminals of a switch with normally open contacts
to the module terminals. The working mode of the sounders at input activation is:
- when the switch is pressed - one second sounders on, one second sounders off;
- when the switch is released - the sounder is off.
Use the left and right arrows to switch over the GENERATES and DELAY fields.
Press the functional button (2) GROUP to enter in submenu for group selection. In the editing field enter the group
number using the up/ down arrow buttons.
All set parameters are confirmed wit ENTER button. The exit to the main screen of DEVICE SETUP menu is with
pressing CANCEL button.
MAGPRO-0i4O – Module with 4 outputs
Use
buttons
and
to select the generated event
FIRE ZONE - Activation from a zone in fire alarm. Set a zone number. In the 'ALARMS' field you can enter a number of
registered fire alarms, when after reaching their count the output will be activated.
The programming is same for all of the outputs.
The number of outputs are distributed into two screens. To program
OUT4 you have to press button MORE >>.
(2) ON/ OFF LED – Press to switch on/ off the device LED.
The installer has to choose an activation event using the up and
down arrows.
Use the left and right arrows to switch over the editable fields.
Other settings are available according the event type - see Table 2.
DEVICE - Activation from a device. Set the loop number and device
address. The 'IN' field refers only to MIO modules.
INPUT GROUP - Activation from a device in group. Set the group
number. The functional button (2) switches alternatively between
the AND and OR logic operation.
36

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents