7.2.3 Disabling Zones

From the main screen of ZONES menu, select a zone number using the up and down arrow buttons and press button
(4) DISABLE. The zone status is changed to DISABLED – the panel stops following the status of the connected
devices to the zone and will not alert for alarms and faults from them. The LED 'Disable' lights up permanently.
To enable the zone press the (4) ENABLE button:

7.2.4 Programming Zone Parameters

Attention: Programming zone parameters is available only from access level 3!
From the main screen of ZONES menu the User can set additional parameters for every zone in the system. To set
zone parameters, select its number using the up/ down arrow buttons and press ENTER button.
In the new sub screen first you can enter a 40-symbol long name for the zone. Use the functional button to set the
operation mode, delays T2 and a group number.

7.2.5 Zone Name

The User can enter a specific name for the zone after entry in the submenu for zone parameters setting. The name can
be up to 40 digits long and it is entered on the second row. Use the left and right arrows to move the cursor. The
symbols (small and capital letters and characters) are set with the up and down arrows. Confirm the entered name with
ENTER button. See also the APPENDIX B – Table for text and symbols available for zone and device names.

7.2.6 Zone Operation Modes

For a zone can be set one operation mode: NORMAL / 2 DEVICES/ DOUBLE.
In NORMAL mode any detector activation within the system generates an alarm event to the respective zone.
In 2 DEVICES mode any detector activation within the system generates a PREALARM event to the respective
zone, but also awaits the activation of another detector from the same zone to generate a FIRE signal. The
RESET command shall disable the FIRE and PREALARM events. If during 5 minutes there is no other fire
alarm signal from other detector in the zone the FIRE alarm will be ignored. The operation of a zone in 2
DEVICES action mode is shown in the examples below.
In DOUBLE mode any detector activation within the system generates a PREALARM event to the respective
zone, but will awaits a second fire signal from the same detector to generate a FIRE signal. The RESET
command shall disable the FIRE and PREALARM events. If during 5 minutes there is no other fire alarm signal
from the same detector in the zone the FIRE alarm will be ignored.
MAGPRO16 Addressable Fire Alarm Panel – Installation and Programming Manual
Note: If at the moment of enabling the zone, there are activated
devices connected to it (fire alarm or fault condition) the panel will
alert for that immediately!
Every pressing of button (2) CHANGE will alternatively change the
operation mode of the zone: NORMAL/ / 2DEVICES/ DOUBLE.
The set mode is confirmed with ENTER button.
29