Zones Menu; General Submenus; Zones Testing - ESP MAGPRO16 Installation And Programming Manual

Intelligent interactive analogue adressable fire alarm control panel
Table of Contents

Advertisement

MAGPRO16 Addressable Fire Alarm Panel – Installation and Programming Manual

7.2. Zones Menu

This menu allows the installer to review and change the status of every zone. In the 'ZONES' menus the installer can
test and enable/ disable the zones. Up to 16 zone numbers are available for settings. The currently edited zone
number is blinking. The menu is accessible from levels 2 and 3.
After entering the menu the screen displays:
The screen displays the current status of every zone with its name (if entered). The editable zone number is blinking.

7.2.1 General Submenus

From the main screen of ZONES menu use the functional digit buttons for direct entry to: (1) GO TO and (2) DEV.
COUNT submenus.
Submenu (1) GO TO. Enter the zone number you want to go. After pressing the button the screen displays:
Submenu (2) DEV. COUNT. The submenu shows information about the total number of the devices in the
respective zone. From the main screen of ZONES menu select a zone number and press button (2). The
screen displays information about the total number of the devices in the selected zone regardless of their
current state.
Example:

7.2.2 Zones Testing

Attention: The zone testing is available only from access level 3!
From the main screen of ZONES menu, select a zone number using the up and down arrow buttons and press button
(3) TEST.
During the test mode the installer activates detectors in the zone (applies heat or smoke) to check their proper
operation. The panel confirms the receiving of fire alarm messages with short sound signals and the number of the
tested zone is blinking.
To stop the zone test, press the (3) 'STOP TEST' functional button. The zone returns to normal operation mode.
After completing the zone testing, reset the panel, as described in item 6.9.
Description of the zone status:
NORMAL – The zone is in normal operation state.
DISABLED – The zone is disabled. See item 7.2.3.
TEST – The zone is in test mode. See item 7.2.2.
FIRE – A device in the zone is in fire.
PRE ALARM – The zone is in preliminary alarm mode. See
the description for '2DEVICES' and 'DOUBLE' operation
mode - item 7.2.6.
FAULT – Trouble in the zone – lost device, broken circuit,
etc.
Use up and down arrows to select zone number. Confirm with
'ENTER' button. The system will automatically go back to the main
screen of ZONES menu as the number of the zone is blinking.
Exit to the main screen of ZONES menu is pressing button ENTER
or CANCEL.
The system will ask for confirmation whether to run the test only for
the selected zone number (button (2) THIS) or for all zones in the
system (button (3) ALL).
The zone(s) status is changed to TEST mode. The LED 'Test' is
lighting on permanently.
28