APPENDIX C — MISCELLANEOUS H-100 INTERNAL ALARMS/WARNINGS
"Strt Inhib:Oil"
– Oil pressure is higher than expected for a stopped engine.
"Overcrank"
– Generator has attempted to start the designated number of times without success.
"Mult Def Digtl"
– More than one Digital Output Function is assigned to the same Digital Output; or A Digital
"Mult Def Analg"
– More than one Analog Input is assigned to the same Analog Output; or An Analog Input is
"WatchDog Fail"
– Firmware was unable to complete all its tasks in the allotted time.
"HW Overspeed"
– Hardware Generator Overspeed circuit has detected a generator overspeed condition.
"System Reset"
– Microprocessor has reset unexpectedly.
"i2t Gen Tmp HI"
– i2t logic has determined alternator temperature is too high.
"300% Rated Cur"
– >300% rated current short present – current is being controlled to 300%.
"Eng Stall RPM"
– Engine has stalled unexpectedly.
"No HTS # Comms" – HTS number '#' is not communicating.
"HTS # SW Fault"
– HTS number '#' failed in its switching attempt.
"HTS # Not Sync"
– HTS number '#' was unable to synchronize with utility in the allotted time.
"HTS # Batt Low"
– HTS number '#' battery is weak and possibly needs replacing.
"No HTS # Batt"
– HTS number '#' battery is not connected.
Output Function is assigned to a reserved Digital Output.
assigned to a reserved Analog Output.