Diagnostics - Generac Power Systems H-100 Technical Manual

Hide thumbs Also See for H-100:
Table of Contents

Advertisement

This is a typical first Generator Parameter page for a
single phase system.
LINE 1:
Phase titles for the voltage and current
– voltage title/current title.
LINE 2:
Line-to-Line voltage for AB and Line-to-
Neutral voltage for A and B in Volts RMS.
LINE 3: Neutral current and Line currents in Amps
RMS.
LINE 4: Generator frequency in Hz followed by the
"More" field to allow page selection.
Press the "ENTER" button.
This is a typical second Generator Parameter page for
a three phase system.
LINE 1: Total system real power in kW.
LINE 2: Total system power factor.
LINE 3: Percentage of the system rated power being
used.
LINE 4: The "More" field to allow page selection.
This is a typical second Generator Parameter page for
a single phase system.
LINE 1: Phase titles for the power and power factor
– Total, A-Neutral, B-Neutral.
LINE 2: Real power in kW – Total system, A-Neutral,
B-Neutral.
LINE 3: Power Factor – Total system, A-Neutral, B-
Neutral.
LINE 4: The "More" field to allow page selection.
Press the "ENTER" button.
General Information
H-100 Control Panel Technical Manual
This is a typical third Generator Parameters page. It
graphically displays the percent of i
currently attained. If the limit is exceeded, an alarm
will be set and the generator will shutdown to protect
the alternator. This display will then show % Temp
>Over Limit<". GenLink can provide more informa-
tion regarding actual limits exceeded. This page is
disabled if the i
t function is disabled.
2

DIAGNOSTICS

There are six System Diagnostic pages. They are digi-
tal inputs page, digital outputs page, two analog input
pages, RS-232 communications status page, and RS-
485 communications status page.
Do the following to view the diagnostics pages:
Press the "MENU" button.
Press the  button twice and the  button.
Press the "ENTER" button.
t thermal limit
2
19