Appendix B
H-100 Control Panel Technical Manual
Number
Default Function Name
63
BAT VOLT LO WARN
64
AVG CURR HI ALRM
65
AVG CURR LO ALRM
66
AVG CURR HI WARN
67
AVG CURR LO WARN
68
AVG VOLT HI ALRM
69
AVG VOLT LO ALRM
70
AVG VOLT HI WARN
71
AVG VOLT LO WARN
72
TOT PWR HI ALARM
73
TOT PWR LO ALARM
74
TOT PWR HI WARN
75
TOT PWR LO WARN
76
GEN FREQ HI ALRM
77
GEN FREQ LO ALRM
78
GEN FREQ HI WARN
79
GEN FREQ LO WARN
80
GEN FREQ FAULT
81
ENG RPM HI ALARM
82
ENG RPM LO ALARM
83
ENG RPM HI WARN
84
ENG RPM LO WARN
85
ENG RPM FAULT
86
SWITCH IN AUTO
87
SWITCH IN MANUAL
88
E-STOP ACTIVE
89
REMOTE START ACT
90
DIG INPUT 05 ACT
BATT CHARGE FAIL
91
DIG INPUT 06 ACT
RUPTURED BASIN
PROP LEAK ACT
LOW FUEL PRS ACT
92
DIG INPUT 07 ACT
LINE POWER ACT
93
DIG INPUT 08 ACT
GEN POWER ACT
94
DIG INPUT 09 ACT
MODEM DCD ACT
95
MODEM ENAB ACT
96
ILC ALR/WRN #1
97
ILC ALR/WRN #2
98
IN WARM UP
99
IN COOL DOWN
100
CRANKING
101
NEED SERVICE
102
SHUTDOWN GENSET
44
Function Description
Battery Voltage has gone below maximum warning limit
Average Current has gone above maximum alarm limit
Average Current has gone below minimum alarm limit
Average Current has gone above maximum warning limit
Average Current has gone below maximum warning limit
Average Voltage has gone above maximum alarm limit
Average Voltage has gone below minimum alarm limit
Average Voltage has gone above maximum warning limit
Average Voltage has gone below maximum warning limit
Total Real Power has gone above maximum alarm limit
Total Real Power has gone below minimum alarm limit
Total Real Power has gone above maximum warning limit
Total Real Power has gone below maximum warning limit
Generator Frequency has gone above maximum alarm limit
Generator Frequency has gone below minimum alarm limit
Generator Frequency has gone above maximum warning limit
Generator Frequency has gone below maximum warning limit
Generator Frequency exceeds nominal limits for valid sensor reading
Engine RPM has gone above maximum alarm limit
Engine RPM has gone below minimum alarm limit
Engine RPM has gone above maximum warning limit
Engine RPM has gone below maximum warning limit
Engine RPM exceeds nominal limits for valid sensor reading
Key Switch in AUTO digital input active
Key Switch in MANUAL digital input active
Emergency Stop Status digital input active
Remote Start digital input active
DI-1, Digital Input #5 active
Battery Charger Fail digital input active
DI-2, Digital Input #6 active
Ruptured Basin digital input active,
Propane Gas Leak digital input active,
Low Fuel Pressure digital input active
DI-3, Digital Input #7 active
Line Power digital input active
DI-4, Digital Input #8 active
Generator Power digital input active
Digital Input #9 active
Modem Carrier Detect digital input active
Modem Enable digital input active
ILC controlled: ILC warning or alarm signal # 1
ILC controlled: ILC warning or alarm signal # 2
Generator is running, but not fully warmed up yet
Generator is running, but cooling down before shutting off.
Generator is starting – the starter is engaged
Maintenance item has expired
Shutdown alarm is active