Use the arrow buttons to change the contrast value
(range is 00 to 37). Pressing the "HOME" button
while in edit mode will return the value to the last
entered value.
Press the "ENTER" button to exit edit mode.
The contrast is now set and can only be changed by
editing the value on this page.
ENABLE GENERAC COMMERCIAL
TRANSFER SWITCH (HTS)
The H-100 Control Panel can control up to four HTSs
via the RS-485 communications port. The H-100
Control Panel is shipped without the HTS control
enabled. If the user has an HTS in their system, they
must enable the HTS via GenLink or the front panel.
If the HTS is not enabled, the generator will not
operate automatically with loss of utility. If the H-100
Control Panel enables a non-existent HTS, there will
be a warning indicated.
Non-HTS switches use the two-wire start inter-
face and do not need enabling by H-100 Control
Panel.

HTS SETUP USING GENLINK

Connect to the H-100 control panel.
Using the "Configuration" pull down, select "Transfer
Switch Configuration" to display the HTS Configuration
screen.
NOTE:
General Information
H-100 Control Panel Technical Manual
The lower left corner contains the HTS number. Use
the "Prev" and "Next" buttons to select the appro-
priate switch number - 1 through 4. If enabling the
switch, check the "Switch Connected" check box
in the middle of the screen. If disabling the switch,
uncheck the "Switch Connected" check box. The
remainder of the settings on this page are described
in the HTS manual.

HTS SETUP USING FRONT PANEL

Press the "MENU" button.
35