H-100 Digital Outputs; H-100 Digital Inputs - Generac Power Systems H-100 Technical Manual

Hide thumbs Also See for H-100:
Table of Contents

Advertisement

H-100 DIGITAL OUTPUTS

H-100
GenLink
Number
Number
1
1
2
2
3
3
4
4
5
5
6
6
7
7
8
8
9
9
10
n/a
11
28
12
25
26
13
31
14
32

H-100 DIGITAL INPUTS

Number
Default Signal Name
1
AUTO SWITCH
2
MANUAL SWITCH
3
EMERGENCY STOP
4
REMOTE START
5
DI1/USR CFG 05
BAT CHRGR FAIL
6
DI2/USR CFG 06
RUPTURED BASIN
PROP GAS LEAK
DI2/FUEL PRESSURE
7
DI3/USR CFG 07
DI3/LINE POWER
8
DI4/USR CFG 08
DI4/GEN POWER
9
MODEM DCD
USR CFG 09
10
MODEM ENABLED
11
GEN OVERSPEED
Signal Description
Starter Relay (reserved)
Fuel Relay (reserved)
Fault Relay (reserved)
13.3L Gas Relay (reserved for ILC on 13.3L gas)
Auxiliary #1
Auxiliary #2
Auxiliary #3
Auxiliary #4
13.3L Ignition Module (reserved for ILC on 13.3L gas)
Overspeed Shutdown (reserved – no software control)
Throttle Driver PWM (reserved for H-100 governed generators)
PreHeat Relay – diesel only (reserved)
Air/Fuel Ratio PWM – gas only (reserved)
AVR Field Control (reserved)
AVR Field Control (reserved)
Signal Description
Key Switch in AUTO
Key Switch in MANUAL
Emergency Stop Status
Remote Start
DI-1,
Battery Charger Fail
DI-2,
Ruptured Basin,
Propane Gas Leak,
Low Fuel Pressure
DI-3,
Line Power
DI-4,
Generator Power
Modem DCD
User confi gurable (reserved if Modem)
Modem Enable
Generator Overspeed Detected
H-100 Control Panel Technical Manual
Appendix B
Connector Pin
J1-23
J1-11
J1-34
J1-22
J2-23
J2-22
J2-33
J2-21
J2-32
J1-10
J1-33
J1-21
J2-20
J2-8
Connector Pin
J2-5
J2-28
J2-16
J2-4
J2-27
J2-15
J2-3
J2-26
J1-14
J1-26
Internal