H-100 CONNECTOR PIN DESCRIPTIONS

J1
Wire
Signal
1
CAN (rtn)
2
CAN (+)
3
810
Gnd
4
805
AN8 (rtn)
5
804
AN8 (+) 0-1V
6
575R
AN5 (rtn)
7
575V
AN5 (+) 4-20mA
8
523R
AN1 (rtn)
9
523V
AN1 (+) 4-20mA
10
R15B
OUT (OC) 10
11
256
OUT (OC) 2
12
0
- Batt (12/24V)
13
CAN (-)
14
811
IN (DB) 9
15
68V
AN2 (+) 4-20mA
16
803
AN9(+) 0-5V
17
766R
AN7 (rtn)
18
766V
AN7 (+) 4-20mA
19
69R
AN3 (rtn)
20
69V
AN3 (+) 4-20mA
21
221/808
OUT (OC)12 (PWM)
22
242
OUT (OC) 4
23
56A
OUT (OC) 1
24
0/shld
RPM sensor (-)
25
79
RPM sensor (+)
26
812
IN (DB) 10
27
AI1R/806/
AN6 (rtn)
754R
28
AI1S/
AN6 (+) 4-20mA
754V
29
573R
AN4 (rtn)
30
573V
AN4 (+) 4-20mA
31
68R
AN2 (rtn)
32
809
+12V (300mA)
33
769
OUT (OC)11 (PWM)
34
445
OUT (OC) 3
35
15B/220B
+ Batt ( 12/24V )
KEY:
OUT (O/C) #1-14 = Digital OUTput, Open Collector (includes
PWM Outputs, AVR Gates)
IN (DB) #1-10
= Digital INput, Buffered (Schmitt Trigger)
"Pulled up"
46
Appendix B
H-100 Control Panel Technical Manual
Description
CAN Bus
CAN Bus (+)
Modem Power (-)
Emissions Sensor/
Fluid Basin Level
Emissions Sensor/
Fluid Basin Level
Fuel Level
Fuel Level
Oil Temperature
Oil Temperature
Overspd Shutdown
Fuel Relay
Panel Power (-)
CAN Bus (-)
Modem DCD
Coolant
Temperature
Battery Charger Cur
Throttle Position
Throttle Position
Oil Pressure
Oil Pressure
Preheat/Air
/Fuel Solenoid
13.3 Gas Relay
Starter Relay
Engine RPM
Engine RPM
Modem Enable
Fuel Press/Ign. Alarm/
Inlet Temp
Fuel Press/
Inlet Temp
Coolant Level
Coolant Level
Coolant Temp
Modem Power (+)
Throttle Driver
Fault Relay
Panel Power ( + )
J2
Wire
Signal
1
391
RS485 (-)
2
388
RS232 (tx)
3
IN7
IN (DB) 7
4
183
IN (DB) 4
5
174
IN (DB) 1
6
224
Vsense 1
7
227
Gnd
8
403
OUT (OC) 14
9
399C
CT3 (-)
10
398C
CT3 (+)
11
399A
CT1 (-)
12
398A
CT1 (+)
13
390
RS485 (+)
14
387
RS232 (rx)
15
567/601
IN (DB) 6
16
R15
IN (DB) 3
17
226
Vsense 3
18
+12V (500 mA)
19
405
Gnd
20
404
OUT (OC) 13
21
OC8
OUT (OC) 8
22
OC6
OUT (OC) 6
23
OC5
OUT (OC) 5
24
SHLD
RS485 (shield)
25
389
RS232 (com)
26
IN8
IN (DB) 8
27
505
IN (DB) 5
28
175
IN (DB) 2
29
225
Vsense 2
30
406
AVR Zero Crossing
31
194
+12V (300 mA)
32
OC9/25
OUT (OC) 9
33
OC7
OUT (OC) 7
34
399B
CT2 ( - )
35
398B
CT2 ( + )
AN #1-7 (+)
= Analog 12V ( 50 mA ) source
AN #1-7 (rtn)
= General purpose analog input ( 4 - 20 mA )
Vsense #1-3
= Voltage sensing input ( 0 - 28.8 VAC)
CT #1-3
= Current Transformer input ( 0 - 3 A AC)
Description
Diagnostic/Rem-An/HTS
GenLink
DI-3/Line Power
Remote Start
Key Switch in AUTO
Phase AB Voltage
Vsense PCB Ground
AVR Gate trigger 'B'
Phase C Current
Phase C Current
Phase A Current
Phase A Current
Diagnostic/Rem-An/HTS
GenLink
DI-2/Ruptured Basin/
Low Fuel Pressure
Emergency Stop
Phase CA Voltage
Vsense PCB
AVR PCB Power (-)
AVR Gate trigger 'A'
Auxiliary 4 Output
Auxiliary 2 Output
Auxiliary 1 Output
Diagnostic/Rem-An/HTS
GenLink
DI-4/Generator Power
DI-1/Battery Charger Fail
Key Switch in MANUAL
Phase BC Voltage
AVR Zero Crossing Input
AVR PCB Power (+)
13.3 Ignition Power
Auxiliary 3 Output
Phase B Current
Phase B Current

Hide quick links: