H-100 Digital Output Functions - Generac Power Systems H-100 Technical Manual

Hide thumbs Also See for H-100:
Table of Contents

Advertisement

Appendix B
H-100 Control Panel Technical Manual

H-100 DIGITAL OUTPUT FUNCTIONS

Number
Default Function Name
1
COMMON ALARM
2
COMMON WARNING
3
GEN RUNNING
4
ALARMS ENABLED
5
READY FOR LOAD
6
GEN READY TO RUN
7
GEN STOPPED-ALRM
8
GEN STOPPED
9
GEN IN MANUAL
10
GEN IN AUTO
11
GEN IN OFF
12
OVERCRANK ALARM
13
OIL INHIBIT ALRM
14
ANNUNC SPR LIGHT
15
OIL TEMP HI ALRM
16
OIL TEMP LO ALRM
17
OIL TEMP HI WARN
18
OIL TEMP LO WARN
19
OIL TEMP FAULT
20
COOL TMP HI ALRM
21
COOL TMP LO ALRM
22
COOL TMP HI WARN
23
COOL TMP LO WARN
24
COOL TMP FAULT
25
OIL PRES HI ALRM
26
OIL PRES LO ALRM
27
OIL PRES HI WARN
28
OIL PRES LO WARN
29
OIL PRES FAULT
30
COOL LVL HI ALRM
31
COOL LVL LO ALRM
32
COOL LVL HI WARN
33
COOL LVL LO WARN
34
COOL LVL FAULT
35
ANALOG 5 HI ALRM
FUEL LVL HI ALRM
36
ANALOG 5 LO ALRM
FUEL LVL LO ALRM
37
ANALOG 5 HI WARN
FUEL LVL HI WARN
38
ANALOG 5 LO WARN
FUEL LVL LO WARN
39
ANALOG 5 FAULT
FUEL LVL FAULT
40
ANALOG 6 HI ALRM
FUEL PRS HI ALRM
INLT TMP HI ALRM
41
ANALOG 6 LO ALRM
FUEL PRS LO ALRM
INLT TMP LO ALRM
42
Function Description
An alarm is active
A warning is active
Generator is running
All alarm hold off delays have expired, so all alarms are enabled
Generator is warmed up and ready to accept power loading
Generator is ready to start
Generator stopped due to a shutdown alarm
Generator is stopped
Generator in MANUAL mode ( key switch in MANUAL or ILC overriden)
Generator in AUTO mode ( key switch in AUTO or ILC overriden )
Generator in OFF mode ( key switch in OFF or ILC overriden )
Generator has unsuccessfully tried to start the designated number of times
Oil pressure too high for a stopped engine
ILC controlled: this function operates the spare remote annunciator light
Oil Temperature has gone above maximum alarm limit
Oil Temperature has gone below minimum alarm limit
Oil Temperature has gone above maximum warning limit
Oil Temperature has gone below maximum warning limit
Oil Temperature sensor exceeds nominal limits for valid sensor reading
Coolant Temperature has gone above maximum alarm limit
Coolant Temperature has gone below minimum alarm limit
Coolant Temperature has gone above maximum warning limit
Coolant Temperature has gone below maximum warning limit
Coolant Temperature sensor exceeds nominal limits for valid sensor reading
Oil Pressure has gone above maximum alarm limit
Oil Pressure has gone below minimum alarm limit
Oil Pressure has gone above maximum warning limit
Oil Pressure has gone below maximum warning limit
Oil Pressure sensor exceeds nominal limits for valid sensor reading
Coolant Level has gone above maximum alarm limit
Coolant Level has gone below minimum alarm limit
Coolant Level has gone above maximum warning limit
Coolant Level has gone below maximum warning limit
Coolant Level sensor exceeds nominal limits for valid sensor reading
Analog Input #5 has gone above maximum alarm limit
Fuel Level
Analog Input #5 has gone below minimum alarm limit
Fuel Level
Analog Input #5 has gone above maximum warning limit
Fuel Level
Analog Input #5 has gone below maximum warning limit
Fuel Level
Analog Input #5 sensor exceeds nominal limits for valid sensor reading
Fuel Level
Analog Input #6 has gone above maximum alarm limit
Fuel Pressure
Inlet Air Temperature
Analog Input #6 has gone below minimum alarm limit
Fuel Pressure
Inlet Air Temperature