Protection Function; Other Control; Sleep Function - Gree KFR-25GW/NaA512 User Manual

Ultra thin split unit series
Table of Contents

Advertisement

indicator light flash, when detecting the frost on the condenser had been defrosted, the indoor, outdoor fan motor, 4-way valve start
to run at the same time, the compressor keep the original running state, the indicator stop flashing.
When electrified the first defrosting time is 9min,then according to the frost situation, to adjust the defrosting time,
if frost is too much that the defrosting time will be long(the max. time is 9min.), if frost is less, the defrosting time
will be short (at least 3min.), when defrosting finished it will quit.
Old defrosting mode (multi-split type series)
When detected there are frost on the condenser, the system will enter into defrosting status, at this time, the compressor continue
to run, outdoor fan motor, 4-way valve, indoor fan motor stop running. The running indicator flash, when the frost on the condenser
had been defrosted or defrosting operation run for 10mins later, the indoor, outdoor fan motors, 4-way valve will start running at the
same time, the compressor keep the running state, the running indicator stop flash, the defrosting procedure finished.

Protection function

Anti-high temperature protection
When detected the evaporator tube temp. is too high, outdoor fan motor stop running;
when tube temp. of evaporator resumed, outdoor fan motor will resume to run.
Noise protection
When to turn off the unit by using "RUN/STOP" , the reversing valve will delayed 2mins to turn off; or mode shift
will delay 2minutes.
Fan mode
In this mode, indoor fan can select Hi, Med, Low and Auto ( Med is default) to run, the compressor, outdoor fan motor,
4-way valve stop running.
In this mode, the temp. setting range is
Auto mode
In this mode, system will accord the changes of ambient temp. to select the running mode (COOL, DRY, HEAT
and FAN). The protection function as the mode of COOL, HEAT.

Other control

Sleep function

When it is cooling and drying, after setting the sleep mode for 1hour, Tset will be increased 1℃; after 2hours, Tset
will be increased 2℃, indoor motor runs at low fan speed.
Compressor
Outdoor fan
Indoor fan
Four-way valve
Running
Compressor
Outdoor fan
Indoor fan
Four-way valve
Running
Tset
Tset
Tset
1hour
2hours
Defrosting
3min. 9min.
Stop
Defrosting
10min.
Stop
.
Setting temp. Tset
2hours above