Interpret Status Indicators

Refer to the following diagram and table for information on how to interpret the
status indicators.
POINT I/O EtherNet/IP Adapter, Series B
Network address
thumbwheels
Ethernet RJ-45 connector
Indicator Status for Modules
Indicator
Status
Module
Off
status
Flashing green
Solid green
Flashing Red
Solid red
Flashing red/green Module self-test.
1734 POINT I/O EtherNet/IP Adapter
0
0 2
Description
No power applied to device
Device needs commissioning due to missing, incomplete, or
incorrect configuration.
Device is operating normally.
Recoverable fault.
Complete firmware update, verify address switches.
Unrecoverable fault has occurred:
• Self-test failure present (checksum failure, or RAMtest failure at
cycle power).
• Firmware fatal error.
Publication 1734-IN042D-EN-P - October 2015
Module status
Network activity
Network status
POINTBus status
System power
Field power
NC
Chas Gnd