8 1734 POINT I/O EtherNet/IP Adapter

Before You Begin

To effectively use your adapter, note the following considerations.

Firmware Backward Compatibility

The 1734-AENT Add-on Profiles are compatible with RSLogix 5000 software version 16,
or greater.
If you use the 1734-AENT adapter with a 1756-ENBT module, use the following required
firmware versions for these bridge modules:
1756-ENBT firmware version 4.006 or greater
1768-ENBT firmware version 2.003 or greater
Add-on Profiles can be downloaded from:
https://www.rockwellautomation.com/rockwellautomation/support/downloads.page

Understand Messaging

Class 3 (Explicit Message) requests through the 1734-AENT adapter to a specific
POINT I/O module do not always receive a response from the I/O modules. Where an
I/O module does not reply to a request, the adapter responds with an error code indicating
a timeout.

Configure Autobaud

The adapter cannot reconfigure an I/O module that you previously configured to operate
at a fixed baud rate. When you reuse a POINT I/O module from another POINT I/O
system, configure the module to autobaud before using it with the adapter.
Publication 1734-IN042D-EN-P - October 2015