Program Example - Mitsubishi Electric MELSEC iQ-F FX55-ASL-M User Manual

Melsec iq-f series aslink
Table of Contents

Advertisement

Program example

Classification
Module label
Label to be defined
(38)
When 'ProgramStart' (M1) is turned on, the values of 'Input information area' (U1\G0) are transferred to 'Input ASLINKER data storage area'
(K4M1000).
The values of 'OutputArea' (K4M2000) are transferred to 'Output information area' (U1\G4096).
After 'Module READY' (U1\G28 b0) turns on, wait at least one second and start the program.
8 PROGRAMMING
64
8.2 Communication of FX5-ASL-M with Slave Module
Label name
FX5ASLM_1.bModuleREADY_D
FX5ASLM_1.bDP_DNShortError_D
FX5ASLM_1.b24V_DPShortError_D
FX5ASLM_1.bTransmissionCableVoltageDdropError_D
FX5ASLM_1.bDP_DNDisconnectionError_D
FX5ASLM_1.uInputInformationArea0_15_D
FX5ASLM_1.uOutputInformationArea0_15_D
Define the global label as follows.
Description
Module READY
DP/DN short error
24V/DP short error
Transmission cable voltage drop error
DP/DN disconnection error
Input information area
Output information area
Device
U1\G28 b0
U1\G28 b1
U1\G28 b2
U1\G28 b3
U1\G28 b4
U1\G0
U1\G4096