■Parameters
Each slave module has the following types of parameters:
• Device parameter (19 types)
These parameters are unique to each slave module. The contents of the parameters vary depending on the types of slave
modules. For details, refer to the specifications of the slave module.
• AnyWireASLINK parameter (3 types)
These parameters are common to all the slave modules connected to AnyWireASLINK.
Name
Module ID
Status details
Sensing level
APPX
84
Appendix 4 Buffer Memory
Read/write
Corresponding buffer
memory area
Un\G12288+n  48
Read/write
(n: 0 to 127)
1st of 48 words
Un\G12327+n  48
Read
(n: 0 to 127)
40th of 48 words
Un\G12328+n  48
Read
(n: 0 to 127)
41th of 48 words
Detailed description
Indicates the slave module ID.
• 0000H to 00FFH: ID of an output slave module
• 0200H to 02FFH: ID of an input slave module or I/O combined slave
module
Indicates the status of the slave module.
The statuses of the slave modules can be checked with the on/off status
of each bit.
■b0: Module power supply status
• On: Slave module voltage drop
• Off: No error
■b1: Sensing level status
• On: Sensing level drop
• Off: No error
■b2 to b15: System area
Indicates the value of a connected sensor.
The value differs depending on the connected slave module.
(Example: An analog value of 0 to 100% is indicated for an ON/OFF
sensor.)