Set type code

The type code - TypeCode (97.01) - is preset in the factory and is write protected.
It identifies the drives current-, voltage-, temperature measurement and its
quadrant type. The type code can be changed as whole or individually.
To change the type code as whole follow the instructions below:
un-protect the type code by means of ServiceMode (99.06) = SetTypeCode
set TypeCode (97.01) = S01-0020-04 to S02-5200-05 (details, see table
below)
The drive's basic type code: DCS800-AAX-YYYY-ZZB
Product family:
Type:
Bridge type:
Module type:
Rated AC Voltage:
Power connection:
Attention:
When using D1, D2, D3 or D4 modules the current and voltage range of the type
code setting is limited to max 1000 ADC and max 600 VAC.
the change of the type code is immediately taken over and ServiceMode
(99.06) is automatically set back to NormalMode
the new values can be seen in group 4
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
DCS800
AA
X
YYYY
ZZ
B
ConvNomCur (4.05),
ConvNomVolt (4.04),
MaxBridgeTemp (4.17) and
QuadrantType (4.15)
3ADW000195R0501 DCS800 Service Manual e e
= S0
Modules
= R0
Rebuild system
= E0
Panel solution
= A0
Enclosed converter
= 1
single bridge (2-Q)
= 2
2 anti parallel bridges (4-Q)
=
converter type current
= 04
230 VAC - 400 VAC
= 05
230 VAC - 525 VAC
= 06
270 VAC - 600 VAC
= 07
315 VAC - 700 VAC
= 08
360 VAC - 800 VAC
= 10
450 VAC - 990 VAC
= 12
540 VAC - 1200 VAC
= -
Standard D1 - D6
= L
Left side D7
= R
Right side D7
= a
Second thyristor type D5, D6