13.3 Protection Control for Heating Operation

13.3.1
Intake Air Temperature Control
Compressor will operate at maximum frequency if below conditions occur:
1
When the indoor intake air temperature is 86°F or above.
13.3.2
Outdoor Air Temperature Control
The maximum current value is regulated when the outdoor air temperature rises above 57.2°F in order to avoid
compressor overloading.
13.3.3
Overload Protection Control
The compressor operating frequency is regulated in accordance to indoor heat exchanger temperature as shown in
below figures.
If the heat exchanger temperature exceeds 140°F, compressor will stop.
13.3.4
Cold Draught Operation
When indoor pipe temperature is low, cold draught operation start where indoor fan speed will be reduced.
13.3.5
Deice Operation
When outdoor pipe temperature and outdoor temperature is low, deice operation start where indoor fan motor and
outdoor fan motor stop and operation LED blinks.
13.3.6

Drain Pump Control

This unit has built-in with drain pump.
Control content
During COOL/DRY mode.
During COOL/DRY mode, drain pump starts 10 seconds after indoor fan motor starts.
o
The drain pump turns ON and turns OFF periodically. (ON or OFF duration depends on room temperature).
o
After COOL/DRY mode, when unit turns OFF (power standby) or changes to HEAT mode.
The drain pump turns ON for 60 seconds immediately.
o
Error judgment
When float switch detects ON signal continuously for 2 minutes 30 seconds, error code H21 are shown.
o
When float switch ON has operated 2 times within 20 minutes, error code H35 are shown.
o
OFF
140ºF
Frequency Reduced
131ºF
Frequency Limited
120.2ºF
Free
58
114.8ºF