Panasonic CS-E9SD3UAW Service Manual page 82

Hide thumbs Also See for CS-E9SD3UAW:
Table of Contents

Advertisement

15.5.11 H30 (Compressor Discharge Temperature Sensor Abnormality)
Malfunction Decision Conditions
During startup and operation of cooling and heating, the temperatures detected by the outdoor discharge pipe
temperature sensor are used to determine sensor errors.
Malfunction Caused
Faulty connector connection.
Faulty sensor.
Faulty PCB.
Troubleshooting
When abnormality indication starts again
Check the connector connection:
Turn off the power
Check the connector connection
Is the connector connection normal?
Check the outdoor discharge pipe temperature sensor:
Plug out connector from t he outdoor unit PCB
Measure the resistance of the outdoor discharge pipe
temperature sensor
Is the measured resistance of the outdoor discharge pipe
temperature sensor matches the value specified in its
characteristic chart?
YES
YES
82
For safety reason and to prevent
component breakdown, always switch
Caution
off the power before remove and
connect the component.
NO
Connector poor contact
Correct the connection
Defect in outdoor discharge pipe
temperature sensor
NO
Replace the outdoor discharge pipe
temperature sensor
Defect in outdoor unit PCB
Replace the outdoor unit PCB

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents