15.5.4
H15 (Compressor Temperature Sensor Abnormality)
Malfunction Decision Conditions
During startup and operation of cooling and heating, the temperatures detected by the outdoor compressor
temperature sensor are used to determine sensor errors.
Malfunction Caused
Faulty connector connection.
Faulty sensor.
Faulty PCB.
Troubleshooting
When abnormality indication starts again
Check the connector connection:
Turn off the power
Check the connector connection
Is the connector connection normal?
Check the outdoor compressor temperature sensor:
Plug out connector from t he outdoor unit PCB
Measure the resistance of the outdoor compressor
temperature sensor
Is the measured resistance of the outdoor compressor
temperature sensor matches the value specified in its
characteristic chart?
Compressor Temp. Sensor
(Thermistor) Characteristics
70
60
50
40
30
20
10
0
68
104
140
Temperature (
YES
YES
176
212
248
284
o
F)
For safety reason and to prevent component
breakdown, always switch off the power
Caution
before remove and connect the component.
NO
Connector poor contact
Correct the connection
NO
Defect in outdoor compressor temperature sensor
Replace the outdoor compressor temperature sensor
Defect in outdoor unit PCB
Replace the outdoor unit PCB