15.5.8
H24 (Indoor Pipe Temperature Sensor 2 Abnormality)
Malfunction Decision Conditions
During startup and operation of cooling and heating, the temperatures detected by the indoor heat exchanger
temperature sensor 2 are used to determine sensor errors.
Malfunction Caused
Faulty connector connection.
Faulty sensor.
Faulty PCB.
Troubleshooting
When abnormality indication starts again
Check the connector connection:
Plug out connector from the indoor unit PCB
Measure the resistance of the indoor pipe temperature
sensor
Is the connector connection normal?
Check the outdoor air temperature sensor:
Plug out connector from t he outdoor unit PCB
Measure the resistance of the outdoor intake air
temperature sensor
Is the measured resistance of the outdoor intake air
temperature sensor matches the value specified in its
characteristic chart?
Sensor (Thermistor)
Characteristics
70
1 Pipe temp. Sensor 1 & 2
60
2 Intake Air Temp. Sensor
50
1
40
2
30
20
10
0
14
32
50
68
Temperature (ºF)
YES
YES
86
104 122
For safety reason and to prevent component
breakdown, always switch off the power
Caution
before remove and connect the component.
Connector poor contact
NO
Correct the connection
Defect in outdoor intake air temperature sensor
NO
Replace the outdoor intake air temperature
sensor
Defect in outdoor unit PCB
Replace the outdoor unit PCB