Register Address*, **
400052
400053
400054
400055
400056
400057
400058
400059
400060
400061
400062
400063
400064
400065
400101-409999
* 6-digit register addressing (400001) is used instead of 5-digit
register addressing (40001) to describe register map. See section
Register Addressing
** Register addresses of the 32-bit parameters cannot be
accessed by using 5-digit register numbers.

Transparent 32-bit

The Transparent 32-bit communication profile provides unaltered
32-bit access to the configured drive profile.
Register Address*, **
400001
400002
Register Data (16-bit)
Native Drive Profile Actual 1
Native Drive Profile Actual 2
DATA IN 1
DATA IN 2
DATA IN 3
DATA IN 4
DATA IN 5
DATA IN 6
DATA IN 7
DATA IN 8
DATA IN 9
DATA IN 10
DATA IN 11
DATA IN 12
Drive Parameter Access (16-bit)
Register Address = 400000 + 100 x Group + Index
Example for Drive Parameter 3.18
400000 + 100 x 3 + 18 = 400318
Register addressing of the 32-bit parameters (not
supported with ACS350 and ACS355):
420000 + 200 x Group + 2 x Index
Example for Drive Parameter 1.27
420000 + 200 x 1 + 2 x 27 = 420254
on page
37
for additional information.
Register Data (16-bit)
Native Drive Profile Control - Least Significant 16-bits
Native Drive Profile Control - Most Significant 16-bits
43
Communication

Advertisement

Table of Contents
loading