ABB FENA-01 Protocol Manual page 32

Protocol manual - modbus/tcp ethernet adapter module
Hide thumbs Also See for FENA-01:
Table of Contents

Advertisement

32
Table 4. The Control Word for the ABB Drives communication
profile. The upper case boldface text refers to the states shown in
Figure 1.
Bit
Name
0
OFF1_
CONTROL
1
OFF2_
CONTROL
2
OFF3_
CONTROL
3
INHIBIT_
OPERATION
4
RAMP_OUT_
ZERO
Communication profiles
Value
1
Proceed to READY TO OPERATE.
0
Stop along currently active deceleration ramp.
Proceed to OFF1 ACTIVE; proceed to READY TO
SWITCH ON unless other interlocks (OFF2, OFF3)
are active.
1
Continue operation (OFF2 inactive).
0
Emergency OFF, coast to stop.
Proceed to OFF2 ACTIVE, proceed to SWITCH-ON
INHIBITED.
1
Continue operation (OFF3 inactive).
0
Emergency stop, stop within time defined by drive
parameter. Proceed to OFF3 ACTIVE; proceed to
SWITCH-ON INHIBITED.
Warning: Ensure motor and driven machine can be
stopped using this stop mode.
1
Proceed to OPERATION ENABLED.
Note: Run enable signal must be active; see drive
documentation. If the drive is set to receive the Run
enable signal from the fieldbus, this bit activates the
signal.
0
Inhibit operation. Proceed to OPERATION
INHIBITED.
1
Normal operation. Proceed to RAMP FUNCTION
GENERATOR: OUTPUT ENABLED.
0
Force Ramp Function Generator output to zero.
Drive ramps to stop (current and DC voltage limits in
force).
STATE/Description