Figure 18 Adjustable Setpoints Parameters - Emerson Liebert NXL 250 kVA Operation And Maintenance Manual

Liebert nxl series. three phase single-module & multi-module
Hide thumbs Also See for Liebert NXL 250 kVA:
Table of Contents

Advertisement

Adjustable Setpoints
These warning and alarm settings can be changed from the touchscreen. Press the box to the left of
each parameter to bring a popup window that will allow the parameter to be changed.
Max Load Alarm
The module will activate a warning when the load is above any of these settings:
• Phase A (%)—10% to 105% (default: 100%)
• Phase B (%)—10% to 105% (default: 100%)
• Phase C (%)—10% to 105% (default: 100%)
• Delay (second)—0 to 60 (default: 5 seconds)
Manual Xfer Bypass Voltage Limits
These set the upper and lower limits that the bypass voltage must be within for a manual transfer to
bypass to be performed.
• Manual Xfer Bypass Voltage Low Limit (%)—1% to 20% (default: 5%)
• Manual Xfer Bypass Voltage High Limit (%)—1% to 15% (default: 5%)
Inlet Air Temp Warning
• Inlet Air Temp Warning—30°C to 40°C (default: 35°C)
NOTE
Temperature will display in both Celsius and Fahrenheit.

Figure 18 Adjustable setpoints parameters

®
Liebert
NXL
16
Operation