How to remove the drain cap
Clip the drain cap by needle-nose
pliers and pull out.
Fig. 10-3-9
How to fix the drain cap
1. Insert hexagonal wrench (4 mm) in a center head.
Fig. 10-3-10
2) Firmly insert the drain cap.
Do not apply lubricating oil
(refrigerant machine oil)
when inserting the drain
cap. Application causes
deterioration and drain
leakage of the plug.
No gap
Fig. 10-3-11
CAUTION
Firmly insert the drain hose and drain cap;
otherwise, water may leak.
In case of right or left piping
• Take off the cap by hand and cut of the slit.
After scribing slits of the bush body with a knife or
a making-off, cut them with a pair of nippers or an
equivalent tool.
In case of bottom right or bottom left piping
• Arter scribing slits of the bush body with a knife or
a making-off pin, cut them with a pair of nippers
or an equivalent tool.
Left-hand connection with piping
Insert a hexagon wrench
Bend the connecting pipe so that it is laid within
(4 mm).
43 mm above the wall surface.
If the connecting pipe is laid exceeding 43 mm above
the wall surface, the indoor unit may unstably be set
on the wall.
When bending the connecting pipe, make sure to
use a spring bender so as not crush the pipe.
Refer to the table below for the bending
radius of each connection pipe.
Bend the connecting pipe within a radius of 30 mm.
To connect the pipe after installation of the unit
(figure)
- 69 -
FILE NO. SVM-17050
Cap
Fig. 10-3-12
Slit
Fig. 10-3-13
Outer diameter
∅ 6.35 mm
∅ 9.52 mm
∅ 12.7 mm
Slit
Bending radius
30 mm
40 mm
50 mm