Quick Installation Guide 00825-0400-4101, Rev AA Rosemount 2051 March 2011 Rosemount 2051 Pressure Transmitter with PROFIBUS PA Rosemount 2051CF Series Flowmeter Transmitter with PROFIBUS PA Start Step 1: Mount the Transmitter Step 2: Consider Housing Rotation Step 3: Set Jumpers and Switches...
Please review the approvals section of the 2051 PROFIBUS PA reference manual for any restrictions associated with a safe installation. • In an Explosion-proof/Flameproof installation, do not remove the transmitter covers when power is applied to the unit.
Quick Installation Guide 00825-0400-4101, Rev AA Rosemount 2051 March 2011 1: M OUNT THE RANSMITTER Liquid Applications 1. Place taps to the side of the line. 2. Mount beside or below the taps. 3. Mount the transmitter so that the drain/vent valves are oriented upward.
Page 4
Quick Installation Guide 00825-0400-4101, Rev AA Rosemount 2051 March 2011 CONTINUED Rosemount 2051C Panel Mount Pipe Mount Coplanar Flange Traditional Flange Rosemount 2051T (1) Panel bolts are customer supplied.
Quick Installation Guide 00825-0400-4101, Rev AA Rosemount 2051 March 2011 CONTINUED Bolting Considerations If the transmitter installation requires assembly of the process flanges, manifolds, or flange adapters, follow these assembly guidelines to ensure a tight seal for optimal performance characteristics of the transmitters. Use only bolts supplied with the transmitter or sold by Emerson as spare parts.
Failure to install proper flange adapter O-rings may cause process leaks, which can result in death or serious injury. The two flange adapters are distinguished by unique O-ring grooves. Only use the O-ring that is designed for its specific flange adapter, as shown below. Rosemount 3051S / 3051 / 2051 / 3095 Flange Adapter O-ring...
Quick Installation Guide 00825-0400-4101, Rev AA Rosemount 2051 March 2011 Inline Gage Transmitter Orientation The low side pressure port (atmospheric reference) on the inline gage transmitter is located in the neck of the transmitter, behind the housing. The vent path is 360° around the transmitter between the housing and sensor.
Quick Installation Guide 00825-0400-4101, Rev AA Rosemount 2051 March 2011 3: S UMPERS AND WITCHES Security After the transmitter is configured, you may want to protect the configuration data from unwarranted changes. Each transmitter is equipped with a security jumper that can be positioned “ON”...
Quick Installation Guide 00825-0400-4101, Rev AA Rosemount 2051 March 2011 4: C ONNECT IRING AND OWER Use the following steps to wire the transmitter: 1. Remove the housing cover on the FIELD TERMINALS side. 2. Connect the power leads to the terminals indicated on the terminal block label.
Page 10
Quick Installation Guide 00825-0400-4101, Rev AA Rosemount 2051 March 2011 CONTINUED Signal Wiring Grounding Do not run signal wiring in conduit or open trays with power wiring, or near heavy electrical equipment. Grounding terminations are provided on the outside of the electronics housing and inside the Terminal Compartment.
Adaptation mode when shipped from the factory. This mode allows the transmitter to communicate with any PROFIBUS PA control host with either the generic Profile GSD (9700) or Rosemount 2051 specific GSD (3333) loaded on the host; therefore, it is not required to change the transmitter identification number at startup.
Page 12
6. IDENTIFICATION # 7. EXIT Class 2 Master The Rosemount 2051 PROFIBUS DD and DTM files are available at www.EmersonProcess.com/Rosemount or by contacting your local salesperson. See Table 2 for steps to configure the transmitter for Pressure measurement. See product manual (00809-0300-4101) for Flow or Level configuration instructions.
3.02 specification and NE 107. See manual for condensed status bit assignment information. The appropriate GSD file must be loaded on the control host - Rosemount 2051 specific (rmt3333.gsd) or Profile 3.02 Generic (pa139700.gsd). These files can be found on www.emersonprocess.com\rosemount or www.profibus.com.
Page 14
Single Seal. C6 Explosion-Proof and intrinsically safe approval. Intrinsically safe for Class I, Division 1, Groups A, B, C, and D when connected in accordance with Rosemount drawings 02051-1008. Temperature Code T3C. For input parameters see control drawing 02051-1008.
Page 15
The manufacturer’s instructions for maintenance shall be followed in detail to assure safety during its expected lifetime. 3. The 2051 does not comply with the requirements of IEC 60079-1 Clause 5 for flameproof joints. Contact Emerson Process Management for information on the dimensions of flameproof joints.
Page 16
The manufacturer’s instructions for maintenance shall be followed in detail to assure safety during its expected lifetime. 3. The 2051 does not comply with the requirements of IEC 60079-1 Clause 5 for flameproof joints. Contact Emerson Process Management for information on the...
Page 17
Quick Installation Guide 00825-0400-4101, Rev AA Rosemount 2051 March 2011 N7 IECEx Type n Certification No. IECEx BAS08.0046X Ex nAnL IIC T4 (T = –40 to 70 °C) = 42.4 Vdc max IP66 Special Conditions for Safe Use (X): The device is not capable of withstanding the 500V insulation test required by Clause 6.8.1 of IEC60079-15.
Quick Installation Guide 00825-0400-4101, Rev AA Rosemount 2051 March 2011 Figure 9. Rosemount 2051 EC Declaration of Conformity EC Declaration of Conformity No: RMD 1071 Rev. A Rosemount Inc. 8200 Market Boulevard Chanhassen, MN 55317-6985 declare under our sole responsibility that the product,...
Page 19
Models 2051CG2, 3, 4, 5; 2051CD2, 3, 4, 5 (also with P9 option); Pressure Transmitters QS Certificate of Assessment - EC No. PED-H-100 Module H Conformity Assessment All other model 2051 Pressure Transmitters Sound Engineering Practice Transmitter Attachments: Diaphragm Seal - Process Flange - Manifold...
Page 20
Quick Installation Guide 00825-0400-4101, Rev AA Rosemount 2051 March 2011 EC Declaration of Conformity No: RMD 1071 Rev. A PED Notified Body Det Norske Veritas (DNV) [Notified Body Number: 0575] Veritasveien 1, N-1322 Hovik, Norway ATEX Notified Bodies for EC Type Examination Certificate...