Reference Manual 00809-0100-4108, Rev CA March 2017 ™ Rosemount 2088, 2090P, and 2090F Pressure Transmitters ® with HART and 1-5Vdc Low Power Protocol...
Page 8
Contents Reference Manual 00809-0100-4108, Rev CA March 2017 Contents...
Page 9
The products described in this document are NOT designed for nuclear-qualified applications. Using non-nuclear qualified products in applications that require nuclear-qualified hardware or products may cause inaccurate readings. For information on Rosemount nuclear-qualified products, contact your local Emerson Sales Representative. Title Page...
Page 10
Installation of this transmitter in an explosive environment must be in accordance with the appropriate local, national, and international standards, codes, and practices. Review the approvals section of the Rosemount 2088, 2090F, 2090P reference manual for any restrictions associated with a safe installation.
The sections in this manual provide information on installing, operating, and maintaining ™ the Rosemount 2088, 2090F, and 2090P. The sections are organized as follows: Section 2: Configuration provides instruction on commissioning and operating Rosemount 2088 Transmitters. Information on software functions, configuration parameters, and online variables is also included.
Reference Manual Introduction 00809-0100-4108, Rev CA March 2017 Models covered The following Rosemount Pressure Transmitters are covered by this manual: 1.2.1 Rosemount 2088G Gage Pressure Transmitter Measures gage pressure up to 4000 psi (275,8 bar) 1.2.2 Rosemount 2088A Absolute Pressure Transmitter Measures absolute pressure up to 4000 psi (275,8 bar) ...
1. Download the latest DD at Emerson.com or FieldCommGroup.org. ™ 2. In the Browse by Member dropdown menu, select Rosemount business unit of Emerson 3. Select desired product. a. Within Table 2-1, use the HART Universal Revision and Device Revision numbers to...
Page 14
Reference Manual Configuration 00809-0100-4108, Rev CA March 2017 Table 2-1. Rosemount 2088 and 2090 with 4–20 mA HART Protocol Device Revisions and Files Device driver Review Review Device identification identification instructions functionality NAMUR NAMUR HART Release date HART Device Manual...
Reference Manual Configuration 00809-0100-4108, Rev CA March 2017 HART installation flowchart ® Figure 2-1. HART Installation Flowchart START HERE Bench Calibration? Field Install Configure Security and Configure for Alarm Verify Pressure (page Mount Transmitter Set Units Review Transmitter page 31 Configuration page 13 page 9...
Pressure (AP) measurements. The Rosemount 2088 utilizes piezoresistive sensor technology for AP and GP measurements. The major components of the Rosemount 2088, 2090F, and 2090P are the sensor module and the electronics housing. The sensor module contains the oil filled sensor system (isolating diaphragm, oil fill system, and sensor) and the sensor electronics.
Page 17
Reference Manual Configuration 00809-0100-4108, Rev CA March 2017 Figure 2-2. LCD/LOI display LCD display LOI display Figure 2-3. Block Diagram Of Operation Signal Processing Microprocessor Digital-to- Sensor linearization Analog Signal Rerange Sensor Module Conversion Temp. Damping Memory Sensor ...
See Figure 4-2 on page 43 for switch location. Note LOI is available with the Rosemount 2088 (option M4) but is not available with the Rosemount 2090F or 2090P. 2.6.1 Configuring on the bench To configure on the bench, required equipment includes a power supply, and a Field Communicator, AMS Device Manager, or an LOI (option M4).
Reference Manual Configuration 00809-0100-4108, Rev CA March 2017 Figure 2-4. Wiring the Transmitter (4–20 mA HART) A. Vdc supply ≥ 250 (necessary for HART communication only) B. R 2.6.2 Configuration tools Figure 2-5. Wiring the Transmitter (1–5 Vdc Low Power) A.
Page 20
Reference Manual Configuration 00809-0100-4108, Rev CA March 2017 Figure 2-6. Device Dashboard 2088 FT 45B Online 1. Overview 2. Configure 3. Service Tools SAVE Configuring with AMS Device Manager Full configuration capability with AMS Device Manager requires loading the most current Device Descriptor (DD) for this device.
Reference Manual Configuration 00809-0100-4108, Rev CA March 2017 Figure 2-7. LOI Configuration Buttons A. Internal configuration buttons B. External configuration buttons Table 2-3. LOI Button Operation Button Left SCROLL Right ENTER 2.6.3 Setting the loop to manual Whenever sending or requesting data that would disrupt the loop or change the output of the transmitter, set the process application loop to manual control.
Fast key sequences for the latest DD are shown in Table 2-4. For Fast Key sequences for legacy DD's contact your local Emerson Representative. Table 2-4. Rosemount 2088 and 2090F/P device dashboard Fast Key sequence From the HOME screen, enter the Fast Key sequences listed Fast Key sequence Function...
Reference Manual Configuration 00809-0100-4108, Rev CA March 2017 2.8.1 Setting pressure units The pressure unit command sets the unit of measure for the reported pressure. Setting pressure units with a Field Communicator From the HOME screen, enter the Fast Key sequence 2, 2, 1, 1, 4 Device Dashboard Fast Keys Setting pressure units with AMS Device Manager...
Page 24
Reference Manual Configuration 00809-0100-4108, Rev CA March 2017 Manually rerange the transmitter by entering range points Entering range points with a Field Communicator From the HOME screen, enter the Fast Key sequence Device Dashboard Fast Keys 2, 2, 2, 1 Entering range points with AMS Device Manager 1.
Page 25
Reference Manual Configuration 00809-0100-4108, Rev CA March 2017 Figure 2-10. Rerange with Applied Pressure Using LOI RERANGE VIEW CONFIG ENTER VALUES ZERO TRIM APPLY VALUES APPLY VALUES APPLY VALUES UNITS RERANGE RERANGE BACK TO MENU EXIT MENU LOOP TEST BACK TO MENU DISPLAY EXIT MENU EXTENDED MENU...
Reference Manual Configuration 00809-0100-4108, Rev CA March 2017 Figure 2-11. Analog Zero and Span Buttons A. Zero and span buttons Note If the transmitter security is on, adjustments to the zero and span will not be able to be made.
Reference Manual Configuration 00809-0100-4108, Rev CA March 2017 Damping with AMS Device Manager 1. Right select the device and select Configure. 2. Select Manual Setup. 3. Within the Pressure Setup box, enter desired damping value and click Send. 4. Carefully read the warning and click Yes if it is safe to apply the changes. Damping with a LOI Reference Figure 2-12...
See “Setting transmitter alarm” on page Table 2-5. Rosemount Alarm and Saturation Values Level 4–20 mA (1–5 Vdc) saturation 4–20 mA (1–5 Vdc alarm ≤...
SCALED VARIAB LOOP TEST ASSIGN PV DISPLAY EXTENDED MENU EXTENDED MENU ALARM SAT VALUES ALARM SAT VALUES ALARM SAT VALUES ROSEMOUNT VALUES EXIT MENU PASSWORD NAMUR VALUES SIMULATE OTHER VALUES HART REV BACK TO MENU BACK TO MENU EXIT MENU EXIT MENU 2.10.2...
Page 30
Reference Manual Configuration 00809-0100-4108, Rev CA March 2017 Scaled Variable. The first use case is to allow custom units to be displayed on the transmitter's LCD/LOI Display. The second use case is to allow custom units to drive the transmitter's 4–20 mA (1–5 Vdc) output. If the user desires custom units to drive the 4–20 mA (1–5 Vdc) output, Scaled Variable must be re-mapped as the primary variable.
Reference Manual Configuration 00809-0100-4108, Rev CA March 2017 Configuring scaled variable using a Field Communicator From the HOME screen, enter the Fast Key sequence 2, 1, 4, 7 Device Dashboard Fast Keys 1. Follow the screen prompts to configure Scaled Variable. a.
Page 32
Reference Manual Configuration 00809-0100-4108, Rev CA March 2017 Re-mapping using a Field Communicator From the HOME screen, enter the Fast Key sequence 2, 1, 1, 3 Fast Keys Re-mapping using AMS Device Manager 1. Right select the device and select Configure. 2.
Reference Manual Configuration 00809-0100-4108, Rev CA March 2017 2.11 Performing transmitter tests 2.11.1 Verifying alarm level If the transmitter is repaired or replaced, verify the transmitter alarm level before returning the transmitter to service. This is useful in testing the reaction of the control system to a transmitter in an alarm state.
Reference Manual Configuration 00809-0100-4108, Rev CA March 2017 Figure 2-17. Performing an Analog Loop Test Using an LOI VIEW CONFIG LOOP TEST ZERO TRIM (1V) SET 4MA UNITS (5V) SET 20MA RERANGE LOOP TEST LOOP TEST SET CUSTOM END LOOP TEST DISPLAY BACK TO MENU EXTENDED MENU...
Reference Manual Configuration 00809-0100-4108, Rev CA March 2017 transmitter, a short pause allows the Field Communicator, AMS Device Manager, or a control system to initiate a request. Choosing burst mode options in HART 5 Message content options: PV only Percent of Range ...
A. HART modem B. Power supply The Rosemount 2088, 2090F, 2090P is set to address zero (0) at the factory, which allows operation in the standard point-to-point manner with a 4–20 mA (1–5 Vdc) output signal. To activate multidrop communication, the transmitter address must be changed to a number from 1 to 15 for HART Revision 5, or 1–63 for HART Revision 7.
Reference Manual Configuration 00809-0100-4108, Rev CA March 2017 Changing transmitter address using a Field Communicator From the HOME screen, enter the Fast Key HART Revision 5 HART Revision 7 sequence 2, 2, 5, 2, 1 2, 2, 5, 2, 2 Device Dashboard Fast Keys Changing transmitter address using AMS Device Manager 1.
Page 38
Reference Manual Configuration 00809-0100-4108, Rev CA March 2017 Configuration...
Installation of this transmitter in an explosive environment must be in accordance with the appropriate local, national, and international standards, codes, and practices. Review the approvals section of the Rosemount 2088, 2090F, 2090P reference manual for any restrictions associated with a safe installation.
Figure 3-6 on page 36 for correct mounting orientation. Installation procedures 3.4.1 Mount the transmitter The following are approximate weights of each transmitter: Rosemount 2088 2.44 lb (1,11 kg) Rosemount 2090F 2.74 lb (1.24 kg) Rosemount 2090P 2.96 lb (1.34 kg). ...
For M20 threads, install conduit plugs to full thread engagement or until mechanical resistance is met. Mounting brackets Rosemount 2088, 2090F, or 2090P transmitters may be panel-mounted or pipe-mounted via an optional mounting bracket (option code B4). See Figure 3-1 on page 32 and for dimensional and mounting configuration information.
Reference Manual Hardware Installation 00809-0100-4108, Rev CA March 2017 Carbon Steel (CS) Head Markings Stainless steel (SST) head markings F593_* *The last digit in the F593_ head marking may be CL A any letter between A and M. Alloy K-500 head marking 3.4.2 Impulse piping Mounting requirements...
Page 46
Reference Manual Hardware Installation 00809-0100-4108, Rev CA March 2017 Figure 3-5. Gas Applications Installation Example Figure 3-6. Steam Applications Installation Example Best practices The piping between the process and the transmitter must accurately transfer the pressure to obtain accurate measurements. There are five possible sources of error: pressure transfer, leaks, friction loss (particularly if purging is used), trapped gas in a liquid line, liquid in a gas line, and density variations between the legs.
Reference Manual Hardware Installation 00809-0100-4108, Rev CA March 2017 The best location for the transmitter in relation to the process pipe is dependent on the process. Use the following guidelines to determine transmitter location and placement of impulse piping: Keep impulse piping as short as possible. ...
3.5.1 Rosemount 2090P Installing the Rosemount 2090P transmitter involves attaching a weld spud to the tapped process vessel, attaching the transmitter to the weld spud, and making electrical connections. If you intend to use an existing weld spud, proceed to the transmitter section of this installation procedure.
Allow adequate cooling between passes. To reduce the chances of distorting the weld spud (for 1.5-in. connection), use a he sink—Rosemount Part Number 02088-0196-0005. 4. Position the weld spud in the vessel hole, place heat sink and tack spud in place using the...
D. Bevelled edge E. Process Rosemount 306 Manifold The Rosemount 306 Integral Manifold is used with the Rosemount 2088 in-line transmitters to provide block-and-bleed valve capabilities of up to 10000 psi (690 bar). Figure 3-9. Rosemount 2088 and 306 In-line Manifold 3.6.1...
Installation of this transmitter in an explosive environment must be in accordance with the appropriate local, national, and international standards, codes, and practices. Review the approvals section of the Rosemount 2088, 2090F, and 2090P reference manual for any restrictions associated with a safe installation.
Reference Manual Electrical Installations 00809-0100-4108, Rev CA March 2017 Local Operating Interface (LOI)/LCD display Transmitters ordered with the LCD display option (M5) or LOI option (M4) are shipped with the display installed. Installing the display on an existing transmitter requires a small instrument screwdriver.
Reference Manual Electrical Installations 00809-0100-4108, Rev CA March 2017 Configuring transmitter security There are four security methods with the Rosemount 2088, 2090F, and 2090P transmitters. Security switch ® HART Lock Configuration Buttons lock LOI password Figure 4-2. 4–20 mA electronics board...
Reference Manual Electrical Installations 00809-0100-4108, Rev CA March 2017 4.4.2 HART lock The HART Lock prevents changes to the transmitter configuration from all sources; all changes requested via HART, LOI, and local configuration buttons will be rejected. The HART Lock can only be set via HART communication, and is only available in HART Revision 7 mode.
Reference Manual Electrical Installations 00809-0100-4108, Rev CA March 2017 Configuring password with Field Communicator From the HOME screen, enter the Fast Key sequence 2, 2, 6, 5, 2 Device Dashboard Fast Keys Configuring password with AMS Device Manager 1. Right select the device and select Configure. 2.
Reference Manual Electrical Installations 00809-0100-4108, Rev CA March 2017 Electrical considerations Note Make sure all electrical installation is in accordance with national and local code requirements. Do not run signal wiring in conduit or open trays with power wiring or near heavy electrical equipment.
Reference Manual Electrical Installations 00809-0100-4108, Rev CA March 2017 Note A minimum loop resistance of 250 Ωs is required to communicate with a Field Communicator. If a single power supply is used to power more than one transmitter, the power supply used, and circuitry common to the transmitters, should not have more that 20 Ωs of impedance at 1200 Hz.
Page 58
Reference Manual Electrical Installations 00809-0100-4108, Rev CA March 2017 Figure 4-6. Wiring the Transmitter (4–20 mA HART) A. DC power supply ≥ 250 (necessary for HART communication only) B. R Figure 4-7. Wiring the Transmitter (1–5 Vdc Low Power) A. DC power supply B.
Reference Manual Electrical Installations 00809-0100-4108, Rev CA March 2017 Note The use of a pin or ferrule wire terminal is not recommended as the connection may be more susceptible to loosening over time or under vibration. 4. Plug and seal unused conduit connection on the transmitter housing to avoid moisture accumulation in the terminal side.
Page 60
The transient protection terminal block can be ordered as an installed option (Option Code T1) or as a spare part to retrofit existing Rosemount 2088, 2090F, and 2090P transmitters in the field. See “Ordering information”...
Page 61
Reference Manual Electrical Installations 00809-0100-4108, Rev CA March 2017 Figure 4-10. Transient protection terminal block A. Lightning bolt location Note The transient protection terminal block does not provide transient protection unless the transmitter case is properly grounded. Use the guidelines to ground the transmitter case. Refer to Figure 4-9 on page Electrical Installations...
Page 62
Reference Manual Electrical Installations 00809-0100-4108, Rev CA March 2017 Electrical Installations...
Switching HART revision ........... page 63 Overview ™ This section contains information on calibrating Rosemount 2088 Pressure Transmitters. Field Communicator, AMS Device Manager and Local Operator Interface (LOI) instructions are given to perform configuration functions.
5.3.1 Field installation tasks 1. Perform sensor zero/lower trim: Compensate for mounting pressure effects a. Refer to Section 3: Rosemount 306 Manifold for manifold operation instructions to properly drain/vent valves 2. Set/check basic configuration parameters a. Output units b.
There are two possible sets of local configuration buttons that can be ordered with the Rosemount 2088 and used to perform trim operations: Digital zero trim and LOI. To access the buttons, loosen screw and rotate top tag until buttons are visible.
Sensor Trim over the full sensor range. Note Do not perform a zero trim on Rosemount 2088A, 2090FA, 2090PA Absolute Pressure Transmitters. Zero trim is zero based, and absolute pressure transmitters reference absolute zero.
Page 68
Reference Manual Operation and maintenance 00809-0100-4108, Rev CA March 2017 Performing a sensor trim with a Field Communicator From the HOME screen, enter the Fast Key sequence and follow the steps within the Field Communicator to complete the sensor trim. 3, 4, 1 Device Dashboard Fast Keys To calibrate the sensor with a Field Communicator using the sensor trim function, perform...
Reference Manual Operation and maintenance 00809-0100-4108, Rev CA March 2017 Performing a digital zero trim (option DZ) A digital zero trim (option DZ) provides the same function as a zero/lower sensor trim, but can be completed in hazardous areas at any given time by simply pushing the zero trim button when the transmitter is at zero pressure.
Reference Manual Operation and maintenance 00809-0100-4108, Rev CA March 2017 Figure 5-4. Recall Factory Trim - Sensor Trim With Local Operator Interface EXTENDED MENU VIEW CONFIG CALIBRAT CALIBRAT CALIBRAT ZERO TRIM DAMPING ZERO TRIM UNITS TRANSFER FUNCT LOWER TRIM RERANGE SCALED VARIAB UPPER TRIM LOOP TEST...
Reference Manual Operation and maintenance 00809-0100-4108, Rev CA March 2017 Performing a 4–20 mA/ 1–5 V output trim with a Field Communicator From the HOME screen, enter the Fast Key sequence and follow the steps within the Field Communicator to complete the 4–20 mA output trim. 3, 4, 2, 1 Device Dashboard Fast Keys Performing a 4–20 mA/ 1–5 V output trim with AMS Device...
Reference Manual Operation and maintenance 00809-0100-4108, Rev CA March 2017 Performing a 4–20/ 1–5 V mA output trim using other scale with a Field Communicator From the HOME screen, enter the Fast Key sequence and follow the steps within the Field Communicator to complete the 4–20 mA output trim using other scale.
Reference Manual Operation and maintenance 00809-0100-4108, Rev CA March 2017 Figure 5-7. Recall factory Trim – Analog Output with LOI EXTENDED MENU VIEW CONFIG CALIBRAT CALIBRAT CALIBRAT ZERO TRIM DAMPING ZERO TRIM UNITS TRANSFER FUNCT LOWER TRIM RERANGE SCALED VARIAB UPPER TRIM LOOP TEST ASSIGN PV...
Reference Manual Operation and maintenance 00809-0100-4108, Rev CA March 2017 5.7.4 Switching HART revision with LOI Navigate to HART REV within the extended menu and select either HART REV 5 or HART REV 7. below to change HART Revision. Figure 5-8 Figure 5-8.
Installation of this transmitter in an explosive environment must be in accordance with the appropriate local, national, and international standards, codes, and practices. ™ Review the approvals section of the Rosemount 2088, 2090F, and 2090P reference manual for any restrictions associated with a safe installation.
Page 76
Reference Manual Troubleshooting 00809-0100-4108, Rev CA March 2017 Table 6-1. Rosemount 2088 2090F, 2090P troubleshooting table for 4–20 mA output Symptom Corrective actions Transmitter milliamp reading is Verify terminal voltage is 10.5 to 42.4 Vdc at signal terminals zero Check power wires for reversed polarity...
Page 77
Reference Manual Troubleshooting 00809-0100-4108, Rev CA March 2017 Table 6-2. Rosemount 2088 troubleshooting for 1–5 Vdc output Symptom Corrective actions Transmitter voltage reading is Verify terminal voltage is 5.8 to 28.0 Vdc at signal terminals zero Check power wires for reversed polarity...
Reference Manual Troubleshooting 00809-0100-4108, Rev CA March 2017 Diagnostic messages Listed in the below sections are detailed table of the possible messages that will appear on ™ either the LCD/LOI display, a Field Communicator, or an AMS Device Manager system. Use the tables below to diagnose particular status messages.
Page 79
Reference Manual Troubleshooting 00809-0100-4108, Rev CA March 2017 Alert name display LOI screen Problem Recommended action screen 1. Check the process and ambient Sensor The sensor temperature has conditions are within –85 to 194 °F Temperature exceeded its safe operating (–65 to 90 °C).
4. Remove all electrical leads and disconnect conduit. 5. Remove the transmitter from the process connection. a. The Rosemount 2088 Transmitter is attached to the process by a single hex nut process connection. Loosen the hex nut to separate the transmitter from the process.
6.4.3 Removing the LOI or LCD display Rosemount 2088 with M4 or M5 option codes have and LOI or LCD display. The transmitter LOI/LCD display are located in the compartment opposite the terminal side. To remove and/or replace the LOI/LCD display, perform the following procedures: 1.
Reference Manual Troubleshooting 00809-0100-4108, Rev CA March 2017 Reassembly procedures 6.5.1 Installing LOI/LCD Display 1. While aligning the captive screws with the respective holes on the electronics board, connect the LCD/LOI display to the electronics board by pressing down firmly. 2.
A.1.3 Dynamic performance specifications Total response Model Update rate times For zero based spans, reference conditions, silicone fill fluid, Rosemount 2088, 145 ms 22 times per second SST materials, digital trim values range points. Applies to 2090F, 2090P ® 4-20 mA HART output only unless otherwise noted.
A.3 Pressure range values Less than ±0.1% of upper range limit when subjected to vibration of peak to peak constant displacement of 4 mm Table A-1. Range Values for Rosemount 2088 (5–15 Hz) and constant acceleration of 2 g (15–150 Hz) and Minimum 1 g (150–2000 Hz)
1387 DZ). See Appendix D: Local Operator Interface. 1000 A.3.3 1-5 Vdc HART low power Operating (output code N for 2088 only) Region Power supply 10.5 42.4 Voltage (Vdc) External power supply required. Standard transmitter The Field communicator requires a minimum loop operates on 5.8 to 28 Vdc with no load.
(-46 to 110 °C) (-45 to 85 °C). materials of construction that can be expected to perform For process well in a wide range of applications. The Rosemount temperatures product information presented is intended as a guide for above 185 °F the purchaser to make an appropriate selection for the (85 °C) below...
Rosemount 2090F A.3.12 Shipping weights 316L stainless steel. Model Output Protocols Available Process connector Rosemount Approximately 2.44 lb. (1,11 kg) Rosemount 2088 2088 Rosemount Approximately 2.96 lb. (1,34 kg) 316L stainless steel 2090F Alloy C-276 Rosemount Approximately 2.74 lb. (1,24 kg)
–14 NPT female B. Nameplate connection connection C. Certification label (located on side) female (PT female), and M20 female also available as options. Figure A-3. Rosemount 2090P 1-in. Flush Mount 5.13 (130) 4.29 (109) max. 3.85 (98) 5.73 (146) 1.03 (26.2) 0.7 (17.8)
Page 90
- or 2-in. Tri Clamp connection C. Transmitter circuity side F. Certification tag Note: M20 1.5 female is also available as option. Dimensions are in inches (millimeters). Figure A-5. Rosemount 2090P 1 -in. Flush Mount 5.13 (130) 3.85 (98) 4.29 (109) max. 4.97 (126) Typical 0.82 (21)
00809-0100-4108, Rev CA A.5 Ordering information Figure A-6. Rosemount 3051P In-Line Pressure Transmitter Ordering Information The starred offerings (★) represent the most common options and should be selected for best delivery. The non-starred offerings are subject to additional delivery lead time.
Page 92
March 2017 00809-0100-4108, Rev CA Figure A-6. Rosemount 3051P In-Line Pressure Transmitter Ordering Information The starred offerings (★) represent the most common options and should be selected for best delivery. The non-starred offerings are subject to additional delivery lead time.
Page 93
March 2017 00809-0100-4108, Rev CA Figure A-6. Rosemount 3051P In-Line Pressure Transmitter Ordering Information The starred offerings (★) represent the most common options and should be selected for best delivery. The non-starred offerings are subject to additional delivery lead time.
Page 94
March 2017 00809-0100-4108, Rev CA Figure A-6. Rosemount 3051P In-Line Pressure Transmitter Ordering Information The starred offerings (★) represent the most common options and should be selected for best delivery. The non-starred offerings are subject to additional delivery lead time.
Page 95
Reference Manual March 2017 00809-0100-4108, Rev CA Table A-3. Rosemount 2090F Pressure Transmitter Ordering Information The starred offerings (★) represent the most common options and should be selected for best delivery. The non-starred offerings are subject to additional delivery lead time.
Page 96
Specifications and Reference Data March 2017 00809-0100-4108, Rev CA Table A-3. Rosemount 2090F Pressure Transmitter Ordering Information The starred offerings (★) represent the most common options and should be selected for best delivery. The non-starred offerings are subject to additional delivery lead time.
Page 97
2090F G 2 S 2D E 1 Table A-4. Rosemount 2090P Pulp and Paper Pressure Transmitter Ordering Information The starred offerings (★) represent the most common options and should be selected for best delivery. The non-starred offerings are subject to additional delivery lead time.
Page 98
March 2017 00809-0100-4108, Rev CA Table A-4. Rosemount 2090P Pulp and Paper Pressure Transmitter Ordering Information The starred offerings (★) represent the most common options and should be selected for best delivery. The non-starred offerings are subject to additional delivery lead time.
Page 99
March 2017 00809-0100-4108, Rev CA Table A-4. Rosemount 2090P Pulp and Paper Pressure Transmitter Ordering Information The starred offerings (★) represent the most common options and should be selected for best delivery. The non-starred offerings are subject to additional delivery lead time.
O@4°C kg/cm Field configurable only, not available for factory calibration or custom Refer to the “Rosemount 2088 Configuration Data Sheet” configuration (option code C9 “Software configuration”). document number 00806-0100-4690. Display and interface options Tagging (3 options available) Digital Display with LOI Standard SST hardware tag is permanently affixed on ...
Page 101
Displays diagnostic messages for local troubleshooting 90-degree rotation capability for easy viewing Configuration buttons Rosemount 2088 now offers internal and external configuration button options. Choosing option D4 will add external Analog Zero and Span configuration buttons Choosing option DZ will add an external Digital Trim ...
Page 102
Reference Manual Specifications and Reference Data March 2017 00809-0100-4108, Rev CA Specifications and Reference Data...
If withstanding a 7 J impact test. paint is ordered through a special option code, 5. The Rosemount 2088/2090 sensor module must be contact the manufacturer for more information. securely screwed in place to maintain the ingress ATEX Intrinsic Safety protection of the enclosure.
1. When fitted with a transient suppression terminal the partition wall. block, the Rosemount 2088 is incapable of passing the 500 V isolation test. This must be taken into 2. The pressure transducers are not intended to be account during installation.
Product Certifications Reference Manual March 2017 00809-0100-4108, Rev CA Special Conditions For Safe Use (X): 5. The product should be used with Ex-certified linear associated apparatus to establish explosion 1. The ambient temperature is as follows: protection system that can be used in explosive gas atmospheres.
Class notations: AUT-UMS, AUT-CCS, Markings: II 2 G Ex de IIC Gb AUT-PORT and AUT-IMS; Pressure Table 5. Conduit Plug Thread Sizes transmitter type 2088 cannot be Thread Identification mark installed on diesel engines SDN Det Norske Veritas (DNV) Type Approval 1.5 –...
March 2017 00809-0100-4108, Rev CA Application: Special Condition for Safe Use (X): 1. The Model 2088 transmitter with the transient Location classes terminal block (Option code T1) will not pass the 500Vrms dielectric strength test and this must be Temperature...
7 J impact test. ≤ ≤ Markings: Ex ia IIC T4 Ga (-55 °C +70 °C) 5. The Rosemount 2088/2090 sensor module must be Table 9. Input Parameters securely screwed in place to maintain the ingress HART protection of the enclosure.
B.2.6 China Special Conditions for Safe Use (X): 1. When fitted with a transient suppression terminal China Flameproof block, the Rosemount 2090 is incapable of passing Certificate: GYJ15.1506X the 500 V isolation test. This must be taken into Standards: GB3836.1-2010, GB3836.2-2010 account during installation.
Product Certifications Reference Manual March 2017 00809-0100-4108, Rev CA Special Conditions for Safe Use (X): IM EAC Intrinsically Safe Certificate: RU C-US.GB05.B.01197 1. The enclosure may be made of aluminum alloy and ≤ ≤ Markings: 0Ex ia IIC T4 Ga X (-55 °C +70 °C) given a protective polyurethane paint finish;...
Page 112
Product Certifications Reference Manual March 2017 00809-0100-4108, Rev CA Table 12. Thread Adapter Thread Sizes Male thread Identification mark 1.5 – 6H –14 NPT –14 NPT –14 NPT –14 NPT Female thread Identification mark 1.5 – 6H –14 NPT –14 NPT PG 13.5 PG 13.5 Special Conditions for Safe Use (X):...
Product Certifications Reference Manual March 2017 00809-0100-4108, Rev CA B.3.2 Canadian standards association (CSA) 02088-1024 Product Certifications...
Page 120
Product Certifications Reference Manual March 2017 00809-0100-4108, Rev CA Product Certifications...
Page 121
Product Certifications Reference Manual March 2017 00809-0100-4108, Rev CA Product Certifications...
Page 122
Product Certifications Reference Manual March 2017 00809-0100-4108, Rev CA Product Certifications...
Field communicator menu trees and Fast Keys Reference Manual March 2017 00809-0100-4108, Rev CA Appendix C Field Communicator menu trees and Fast Keys Field communicator menu trees ......... . page 113 Field communicator Fast Keys .
Page 124
Field communicator menu trees and Fast Keys Reference Manual March 2017 00809-0100-4108, Rev CA Figure C-2. Field Communicator menu tree: configure - guided setup Device Tagging 1 Tag 2 Long Tag 3 Description 4 Message 5 Date Basic Setup Units of Measure/Damping Units of Measure 1 Device Tagging 1 Units of Measure...
Page 125
Field communicator menu trees and Fast Keys Reference Manual March 2017 00809-0100-4108, Rev CA Figure C-3. Field Communicator menu tree: configure - manual setup Pressure Setup Set Range Points 1 Pressure 1 Primary Variable 2 Upper Range Value 2 Upper Range Value 3 Lower Range Value 3 Lower Range Value 4 Pressure Units...
Page 126
Field communicator menu trees and Fast Keys Reference Manual March 2017 00809-0100-4108, Rev CA Figure C-4. Field Communicator menu tree: configure - alert setup Home 1 Overview 2 Configure Configure 3 Service Tools 1 Guided Setup 2 Manual Setup 3 Alert Setup Pressure Alert Alert Setup 1 Configure Alert...
Field communicator menu trees and Fast Keys Reference Manual March 2017 00809-0100-4108, Rev CA Figure C-5. Field Communicator menu tree - service tools Active Alerts Pressure 1 Refresh Alerts 1 Pressure 2 Active Alert 1 2 Status 3 Active Alert 2 4 Etc.
Page 128
Field communicator menu trees and Fast Keys Reference Manual March 2017 00809-0100-4108, Rev CA Table C-1. Device revision 9 and 10 (HART7), DD revision 1 Fast Key sequence Fast Key sequence Function HART 7 HART 5 Range Values 2, 2, 2, 1 2, 2, 2, 1 ...
Local Operator Interface Reference Manual March 2017 00809-0100-4108, Rev CA Appendix D Local Operator Interface LOI menu tree ............page 119 LOI menu tree - extended menu .
EXIT MENU PRESSURE SET PV SCALED SET PV BACK TO MENU EXIT MENU OTHER VALUES ALARM SAT VALUES HIGH ALARM ROSEMOUNT VALUES LOW ALARM NAMUR VALUES HIGH SATURATION OTHER VALUES LOW SATURATION BACK TO MENU BACK TO MENU EXIT MENU...
Local Operator Interface Reference Manual March 2017 00809-0100-4108, Rev CA Number entry Floating-point numbers can be entered with the LOI. All eight number locations on the top line can be used for number entry. Refer to Table 2-3 on page 11 for LOI button operation.
Local Operator Interface Reference Manual March 2017 00809-0100-4108, Rev CA Text entry 1. Text can be entered with the LOI. Depending on the edited item, up to eight locations on the top line can be used for text entry. Text entry follows the same rules as the number entry rules in “LOI menu tree”...
Page 133
Index Reference Manual March 2017 00809-0100-4108, Rev CA Index ........Address Impulse piping .
Page 134
Index Reference Manual March 2017 00809-0100-4108, Rev CA ........31 Recall factory trim Terminal Side .
Page 136
Jebel Ali Free Zone - South 2 The Emerson logo is a trademark and service mark of Emerson Electric Co. Rosemount and Rosemount logotype are trademarks of Emerson. Dubai, United Arab Emirates DTM is a trademark of the FDT Group.
Need help?
Do you have a question about the 2088 and is the answer not in the manual?
Questions and answers