For information on Rosemount nuclear-qualified products, contact your local Rosemount sales representative. Rosemount, the Rosemount logotype, and SMART FAMILY are registered trademarks of Rosemount Inc. PlantWeb is a trademark of the Fisher-Rosemount group of companies. HART is a registered trademark of the HART Communication Foundation.
Flowtube Connections ........2-14 Rosemount Flowtubes ....... . 2-14 Flowtubes of Other Manufacturers .
Page 6
Diagnostics and Service ........Analog Output Test ........Pulse Output Test .
Page 7
APPENDIX B Rosemount Flowtubes ........Model 8705/8707/8711 Flowtubes to Wiring Diagrams Model 8712C/U Transmitter .
Page 8
Fischer And Porter Flowtubes ......B-10 Model 10D1418 Flowtube to Model 8712U Transmitter ..B-10 Model 10D1419 Flowtube to Model 8712U Transmitter .
Section Introduction MANUAL SCOPE The Series 8700 Magnetic Flowmeter System combines a Rosemount magnetic flowmeter flowtube and Rosemount magnetic flowmeter transmitter. This manual covers the Model 8712C/U/H Magnetic Flowmeter Transmitter. For specific magnetic flowtube information, refer to the Series 8700 Magnetic Flowmeter Flowtubes manual (document number 00809-0100-4727).
Model 8712C/U/H Magnetic Flowmeter Transmitters SYSTEM DESCRIPTION A Rosemount Series 8700 Magnetic Flowmeter System measures volumetric flow rate by detecting the velocity of a conductive liquid that passes through a magnetic field. The system consists of two major assemblies: the Model 8705, the Model 8707 High-Signal, or Model 8711 Magnetic Flowmeter Flowtube combined with a magnetic flowmeter transmitter.
FM or CSA approval. Do not connect a Model 8712C/U/H to a non-Rosemount flowtube that is located in an explosive atmosphere. Failure to comply could result in an electrical spark or an explosion.
(see Figure 2-1). The transmitter should be mounted in an upright position. If the Model 8712C/U/H is mounted separately from the flowtube, it is not subject to limitations that might apply to the flowtube. For considerations regarding the installation of the flowtube, please refer to the flowtube manual (document number 00809-0100-4727).
Pipe Mounting To mount the transmitter on a pipe: 1. Attach the mounting plate to the pipe using the mounting hardware. 2. Attach the Model 8712C/U/H to the mounting plate using the mounting screws. Surface Mounting To surface mount the transmitter: 1.
For further information on 4–20 mA external power, see Connect 4–20 mA Loop External Power Source on page 2-10. There is a jumper on the Model 8712C/U/H that allows the user to lock Transmitter Security out any configuration changes attempted on the transmitter. No changes to the configuration are allowed when the jumper is in the ON position.
Jumpers: Pull the jumper off of its current setting and connect to the desired setting. 5. Close the housing door and tighten the housing door screw. FIGURE 2-2. Model 8712C/U/H Electronics Board and Hardware Switches/Jumpers Transmitter Security Failure...
Model 8712C/U/H Magnetic Flowmeter Transmitters Conduit Connections Both the flowtube and transmitter junction boxes have ports for ¾–inch NPT conduit connections. If some of these ports are not being used, conduit seals will need to be installed. In some cases, conduits may also require drainage if there is a possibility of moisture build-up in the line.
Page 17
Cables to be used in the conduit for coil drive and electrode connections Conduit Cables must meet the standards shown in Table 2-1. TABLE 2-1. Recommended Cable Specifications Transmitt er Input Power Description Rosemount Part Number Signal Cable (20 AWG) 08712-0061-0001 Belden 8762, Alpha 2411 equivalent Coll Drive Cable (14 AWG) 08712-0060-0001...
Page 18
Model 8712C/U/H Magnetic Flowmeter Transmitters The Model 8712C/U/H transmitter is designed to be powered by 10–30 V Transmitter Input Power dc, 115 V ac, or 230 V ac. The seventh and eighth digits in the transmitter model number designates the appropriate power supply requirement.
FIGURE 2-5. Supply Current versus Input Voltage Surge Nominal Input Voltage (Volts) OPTIONS, If your application of the Model 8712C/U/H includes the use of options such as multidrop communications, positive zero return (PZR), CONSIDERATIONS, AND auxiliary output control, or pulse output, certain requirements may PROCEDURES apply in addition to those previously listed.
Model 8712C/U/H Magnetic Flowmeter Transmitters Connect 4–20 mA Loop The 4–20 mA output loop provides the process variable output from the transmitter. Its signal may be powered internally or externally. The External Power Source default position of the internal/external analog power jumper is in the internal position.
Installation Connect Pulse Output The pulse output function provides an optically isolated switch-closure frequency output signal that is proportional to the flow through the Power Source flowtube. The signal is typically used in conjunction with an external totalizer or control system. The following requirements apply: Supply Voltage: 5 to 24 V dc Load Resistance: 1,000 to 100 k ohms (typical...
Model 8712C/U/H Magnetic Flowmeter Transmitters Connect Auxiliary The auxiliary output control function allows you to externally signal a zero flow or reverse flow condition. The following requirements apply: Output Control Supply Voltage: 5 to 24 V dc Maximum Power: 5.75 watts...
Installation Connect Positive Zero The PZR function allows the transmitter output to be forced to a zero flow rate signal. While in this state, the transmitter will not react to Return (PZR) Power Source input changes. A zero flow rate signal appears until the PZR signal is removed.
CONNECTIONS Rosemount Flowtubes To connect the transmitter to a Rosemount flowtube, refer to the appropriate wiring diagram in Appendix B. The calibration procedure listed below is not required for use with Rosemount flowtubes. Flowtubes of Other Before connecting another manufacturer’s flowtube to the Model 8712U...
Installation APPLYING POWER All magnetic flowmeter system connections must be completed before power is applied to the system. Check the flowmeter connections between flowmeter and flowtube to be sure they are correct. Check the connections between the power supply and the system to be sure they are correct.
Model 8712C/U/H Magnetic Flowmeter Transmitters Installation Check Use this guide to check new installations of Rosemount magnetic flowmeter systems that appear to malfunction. and Guide Before You Begin Be sure that power to your system is off before beginning these checks.
Page 27
If performing these checks and making any necessary adjustments to your system does not solve the problem, or for specific instructions on making these adjustments, see Table 5-1 on page 5-2 and Table 5-2 on page 5-3 or contact your Rosemount service representative. 2-17...
Page 28
Model 8712C/U/H Magnetic Flowmeter Transmitters 2-18...
Local Operator Interface LOCAL OPERATOR The optional Local Operator Interface (LOI) provides an operator communications center for the Model 8712C/U/H. By using the LOI, the INTERFACE operator can access any transmitter function for changing configuration parameter settings, checking totalized values, or other functions. The LOI is integral to the transmitter housing.
Rosemount Model 8712C/U/H Magnetic Flowmeter Transmitters Data Entry The LOI keypad does not have numerical keys. Numerical data are entered by the following procedure. 1. Access the appropriate function. 2. Use SHIFT to highlight the digit you want to enter or change.
Page 31
Function Performed Keys Tube Calibration Number Identifies the calibration number when using Rosemount flowtubes, or other manufacturers’ flowtubes calibrated at the Rosemount factory Tube Size Specifies the flowtube size and identifies the corresponding maximum flow (0.15- through 60-inch line sizes)
Rosemount Model 8712C/U/H Magnetic Flowmeter Transmitters DIAGNOSTIC MESSAGES The following error messages may appear on the LOI screen. To correct the problem, complete the steps indicated. If the problem persists, contact your sales or service representative. A letter “R” representing reverse flow and a letter “T”...
“DIGITAL TRIM FAILURE” message may appear. If this message occurs, no values were changed in the transmitter. Simply power down the Model 8712C/U/H to clear the message. If the trim was completed or no error message appears, correction requires a Model 8714B or Model 8714C.
Model 8712C/U/H Magnetic Flowmeter Transmitters PROCESS VARIABLES The process variables measure flow in several ways that reflect your needs and the configuration of your flowmeter. When commissioning a HART Fast Keys 1, 1 flowmeter, review each process variable, its function and output, and...
Device Software Functions DIAGNOSTICS AND SERVICE Analog Output Test The analog output test allows you to drive the transmitter output to a desired electrical current output on terminals 7 and 8. This capability HART Fast Keys 1, 1, 3 allows you to check the entire current loop prior to start-up. On the LOI LOI Key Aux.
This procedure is rarely needed by customers. It is only HART Fast Keys 1, 2, 4, 3 necessary if you suspect the Model 8712C/U/H is no longer accurate. LOI Key Aux. Function A Rosemount Model 8714 Calibration Standard is required to complete an electronics trim.
Universal Auto Trim flowtubes that were not calibrated at the Rosemount factory. (This (Model 8712U Only) function is not available for the Model 8712C/H.) The function is HART Fast Keys 1, 2, 4, 5 activated as one step in a procedure known as in-process calibration. If...
For example, if gal/min is selected, the Model 8712C/U/H totalizes and provides a pulse output in gallons. URV (Upper Range Value) The upper range value (URV), or analog output range, is preset to 30 ft/s at the factory.
Device Software Functions LRV (Lower Range Value) Reset the lower range value (LRV), or analog output zero, to change the size of the range (or span) between the URV and LRV. Under normal HART Fast Keys 1, 3, 4 circumstances, the LRV should be set to a value near the minimum LOI Key Aux.
16-digit tube calibration number exists for your flowtube. NOTE Be sure the calibration number reflects a calibration to a Model 8712C. If the number reflects calibration to a Model 8712, accuracy of the system may be compromised.
1000 Hz. With the 110 percent overrange capability, the absolute limit is 1100 Hz. For example, if you want the Model 8712C/U/H to pulse every time 0.01 gallons pass through the flowtube, and the flow rate is 1000 gal/min, you will exceed the 1000 Hz...
Model 8712C/U/H Magnetic Flowmeter Transmitters Pulse Width The width, or duration, of the pulse width can be adjusted to match the requirements of different counters or controllers HART Fast Keys 1, 4, 3, 2, 2 (see Figure 4-1). LOI Key Aux.
0.05 gal/pulse 1 Pulse 0.05 gallon Special Units The Model 8712C/U/H provides a selection of standard units configurations that meet the needs of most applications (see Flow Rate HART Fast Keys 1, 3, 2, 2 Units on page 4-6). If your application has special needs and the LOI Key Aux.
The HART Communicator and HART Fast Keys 1, 3, 2, 2, 5 Model 8712C/U/H will display a special units designator as the units LOI Key Aux. Function format for your primary variable. The actual special units setting you define will not appear.
Device Software Functions Measure Gross Total Measure gross total provides the output reading of the totalizer. This value is the amount of liquid or gas that has passed through the HART Fast Keys 1, 1, 4, 1 flowmeter since the totalizer was last reset LOI Key Totalizer Start Totalizer...
Signal Processing Control On/Off When ON is selected, the Model 8712C/U/H output is derived using a HART Fast Keys 1, 4, 4 running average of the individual flow inputs. Signal processing is a LOI Key Aux.
10 seconds. In some cases this may be unacceptable. By setting the time limit, you can force the Model 8712C/U/H to clear the value of the running average and re-establish the output and average at the new flow rate once the time limit has elapsed.
Model 8712C/U/H Magnetic Flowmeter Transmitters MISCELLANEOUS The miscellaneous functions listed below are used in flowtube calibration and other procedures. The transmitter gain, flowtube gain, FUNCTIONS and coil current functions can be accessed only with the Model 8712U transmitter. Coil Current Based on the flowtube resistance and inductance, the coil current is automatically set when a universal auto trim is performed.
Device Software Functions Liner Material Liner Material enables you to select the liner material for the attached flowtube. This variable only needs to be changed if you have replaced HART Fast Keys your flowtube. LOI Key XMTR INFO Liner Materials ®...
Contact Rosemount product support with specific requirements for multidrop applications. The HART Communicator can test, configure, and format a Model 8712C/U/H multidrop installation the same way as it can a Model 8712C/U/H in a standard point-to-point installation. FIGURE 4-2. Typical Multidrop Network...
Section Troubleshooting SAFETY MESSAGES Instructions and procedures in this section may require special precautions to ensure the safety of the personnel performing the operations. Refer to the following safety messages before performing any operation in this section. Failure to follow these installation guidelines could result in death or serious injury: Installation and servicing instructions are for use by qualified personnel only.
Model 8712C/U/H Magnetic Flowmeter Transmitters BASIC TRANSMITTER TROUBLESHOOTING TABLE 5-1. Basic Troubleshooting–Model 8712C/U/H Corrective Action Symptom Potential Cause Output at 0 mA No power to transmitter Check power source and connections to the transmitter Blown fuse Check the fuse and replace with an appropriately rated fuse, if necessary Electronics failure Replace the electronics boards –...
Troubleshooting ADVANCED TRANSMITTER TROUBLESHOOTING TABLE 5-2. Advanced Troubleshooting–Model 8712C/U/H Symptom Potential Cause Corrective Action Does not appear to be within Transmitter, control system, or other Check all configuration variables for the transmitter, flowtube, rated accuracy receiving device not configured properly communicator, and/or control system –...
Page 54
Model 8712C/U/H Magnetic Flowmeter Transmitters TABLE 5-2. Advanced Troubleshooting–Model 8712C/U/H Symptom Potential Cause Corrective Action Meter output is unstable Medium to low conductivity fluids (10–25 Eliminate cable vibration: micromhos/cm) combined with cable • Integral mount vibration or 60 Hz interference •...
During the entire test, all outputs are driven to full-scale, 20 mA and 1,000 Hz. The test requires about ten seconds to complete. FLOWTUBE The Model 8712C/U/H, Model 8732C, or Model 8742C Magnetic Flowmeter Transmitters perform self diagnostics on the entire TROUBLESHOOTING magnetic flowmeter system: the transmitter, the flowtube, and the interconnecting wiring.
Page 56
Model 8712C/U/H Magnetic Flowmeter Transmitters TABLE 5-3. Flowtube Troubleshooting Test A–Flowtube Coil Step 1 Step 2 Step 3 Disconnect power from the transmitter Measure the resistance across wires 1 A reading outside this range indicates by removing the fuse. Disconnect wires...
(see page 4-5) on the transmitter. 2. Increase the analog damping to 5 seconds. 3. Activate digital signal processing. 4. Consult Rosemount Sales Representative about using a High- Signal Magnetic Flowmeter System. REPLACEMENT This section includes instructions for replacing the electronics board. If...
Page 58
5. Disconnect the cable at the LOI Connector as shown in Figure 5-2. The power supply transformer may be left in the unit unless it is suspected to be faulty. FIGURE 5-2. Model 8712C/U Captive Screws and Connectors Power Supply Transformer LOI Connector Power Connector...
Troubleshooting Installing the Electronics 1. Make sure that the large power supply transformer in the upper left hand corner is present. Transmitters operating by dc power do not have a transformer. 2. Holding the board component side down, connect the Power Connector and the Terminal Block Connectors.
Model 8712C/U/H Magnetic Flowmeter Transmitters Install the LOI Complete the following steps to install a new LOI electronics assembly. Electronics Assembly 1. Disconnect power from the transmitter. 2. Connect the LOI keypad connector to the LOI electronics assembly and snap it into place.
SPECIFICATIONS Functional Specifications Flowtube Compatibility Model 8712C is compatible with all Rosemount flowtubes – Model 8705, Model 8707, and Model 8711. The Model 8712U is also compatible with AC and DC powered flowtubes of other manufacturers. The Model 8712H is only compatible with Model 8707 high-signal flowtube.
Page 62
Model 8712C/U/H Magnetic Flowemter Transmitters Storage –22 to 176 °F (–30 to 80 °C) Humidity Limits 0–100% RH at 120 °F (49 °C), decreases linearly to 10% RH at 130 °F (54 °C) Enclosure Ratings NEMA 4X, CSA Enclosure Type 4X...
Model 8712U transmitters and other manufacturer’s flowtubes can be calibrated at known process conditions or at the Rosemount NIST-Traceable Flow Facility. Transmitters calibrated on site require a two-step procedure to match the known flow rate.
0.1% of span Model 8712U with Other Manufacturers’ Flowtubes When calibrated in the Rosemount Flow Facility, system accuracies as good as 0.5% of rate can be attained. Analog output has the same accuracy as frequency output, plus an additional 0.05% of span.
Page 65
Specifications Electrical Connections Three ¾–14 NPT connections provided on the base of the transmitter; screw terminals provided for all of the connections; power wiring connected to the transmitter only; remote mounted transmitters require only a single conduit connection to the flowtube; integrally mounted transmitters are factory-wired to the flowtube Cable Requirements for Remote-Mount Transmitters Transmitter Input Power...
• • Typical Model Number: 8712C R 12 N 0 (1) NAUMUR-compliant operation; alarm latch operations are pre-set at the factory and can not be changed to standard operation in the field. (2) Option Code must be ordered for both flowtube and transmitter.
Transmitter and Flowtube Accessories – U-bolt for 2-inch Pipe Mount Kit (includes 1 each) C098300002 Multi-Point Reference Calibration Standard – (for use with Model 8712C, Model 8712U, or Model 8732C Transmitters) 8714DQ4 – Flowtrol Totalizer (Kessler-Ellis) 08712-0400-0002 – Spare Model 8714D Cable (for Model 8712C or 8712U transmitters) 08714-0205-0001 –...
Appendix HART Communicator INTRODUCTION Included in this appendix • Menu tree structure • Fast key sequence features • Description of the HART Communicator keypad • Connections and hardware • Basic features • Functions of menus • Diagnostic messages NOTE This appendix provides a brief summary of the HART Communicator and is not meant to replace the HART Communicator manual.
Page 70
Model 8712C/U/H Magnetic Flowmeter Transmitters FIGURE A-1. HART Communicator Menu Tree for Model 8712C/U/H 1 Flow Rate 1 Measure Gross Total 1 PROCESS 2 Measure Net Total 2 Percent of Range VARIABLE 3 Analog Output 3 Measure Reverse Total 4 Start Totalizer...
Page 71
HART Communicator TABLE A-1. HART Fast Key Sequences Function HART Fast Key Function HART Fast Key Analog Output 1, 1, 3 Number Preambles 1, 4, 3, 5, 2 Auto Zero Trim 1, 2, 4, 4 Percent of Range 1, 1, 2 Auxiliary Output 1, 4, 3, 3 Poll Address...
Page 72
Model 8712C/U/H Magnetic Flowmeter Transmitters CONNECTIONS AND The HART Communicator exchanges information with the transmitter from the control room, the instrument site, or any wiring termination HARDWARE point in the loop. Be sure to install the instruments in the loop in accordance with intrinsically safe or nonincendive field wiring practices.
HART Communicator FIGURE A-4. Connecting the HART Communicator with the Optional Load Resistor NOTE Loop must be broken to insert the optional 250 ohm resistor. Model 8712U Fuse Optional 250 ohm load resistor BASIC FEATURES The basic features of the HART Communicator include Action Keys, Function Keys, and Alphanumeric and Shift Keys.
Model 8712C/U/H Magnetic Flowmeter Transmitters Action Keys The Action Keys As shown in Figure A-5, the action keys are the six blue, white, and black keys located above the alphanumeric keys. The function of each key is described as follows: ON/OFF Key Use this key to power the HART Communicator.
HART Communicator Data Entry Some menus require data entry. Use the Alphanumeric and Shift keys to enter all alphanumeric information into the HART Communicator. If you press an Alphanumeric key alone from within an edit menu, the bold character in the center of the key appears. These large characters include the numbers zero through nine, the decimal point (.), and the dash symbol (—).
Model 8712C/U/H Magnetic Flowmeter Transmitters MENUS AND FUNCTIONS The HART Communicator is a menu driven system. Each screen provides a menu of options that can be selected as outlined above, or provides direction for input of data, warnings, messages, or other instructions.
HART Communicator Diagnostic Messages The following is a list of messages used by the HART Communicator (HC) and their corresponding descriptions. Variable parameters within the text of a message are indicated with <variable parameter>. Reference to the name of another message is identified by [another message].
Page 78
Model 8712C/U/H Magnetic Flowmeter Transmitters TABLE A-2. Diagnostic Messages Message Description No Valid Items The selected menu or edit display contains no valid items. OFF KEY DISABLED Appears when the user attempts to turn the HC off before sending modified data or before completing a method On-line device disconnected with unsent data –...
Wiring Diagrams The wiring diagrams in this section illustrate the proper connections between the Model 8712C/U/H and most flowtubes currently on the market. Specific diagrams are included for most models, and where information for a particular model of a manufacturer is not available, a generic drawing pertaining to that manufacturers’...
Model 8712C/U/H Magnetic Flowmeter Transmitters ROSEMOUNT FLOWTUBES Model 8705/8707/8711 Connect coil drive and electrode cables as shown in Figure B-1. Flowtubes to Model 8712C/U Transmitter FIGURE B-1. Wiring Diagram to Model 8712C/U/H Transmitter TABLE B-1. Rosemount Model 8705/8707/8711 Flowtube Wiring Connections...
Connect coil drive and electrode cables as shown in Figure B-2. Flowtube to Model 8712H High-Signal Transmitter FIGURE B-2. Wiring Diagram to Model 8712H High-Signal Transmitter TABLE B-2. Rosemount Model 8707 Flowtube Wiring Connections Rosemount Rosemount Model Model 8712H 8707 Flowtubes...
Model 8712C/U/H Magnetic Flowmeter Transmitters Model 8701 Flowtube to Connect coil drive and electrode cables as shown in Figure B-3. Model 8712U Transmitter FIGURE B-3. Wiring Diagram for Rosemount Model 8701 Flowtube and Rosemount Model 8712U Transmitter ROSEMOUNT MODEL ROSEMOUNT MODEL...
FIGURE B-4. Wiring Diagram for Rosemount 8705 Flowtube and Rosemount Model 8712U Transmitter ROSEMOUNT MODEL 8705 FLOWTUBE ROSEMOUNT MODEL 8712U TRANSMITTER TABLE B-4. Rosemount Model 8705 Flowtube Wiring Connections Rosemount Rosemount Model Model 8712U 8705 Flowtubes This is a pulsed dc magnetic flowmeter. Do...
Model 8712C/U/H Magnetic Flowmeter Transmitters Model 8711 Flowtube to Connect coil drive and electrode cables as shown in Figure B-5. Model 8712U Transmitter FIGURE B-5. Wiring Diagram for Rosemount Model 8711 Flowtube and Rosemount Model 8712U Transmitter ROSEMOUNT MODEL 8711 FLOWTUBE...
Connect coil drive and electrode cables as shown in Figure B-6. Model 5000 Flowtube to Model 8712U Transmitter FIGURE B-6. Wiring Diagram for Brooks Flowtube Model 5000 and Rosemount Model 8712U BROOKS MODEL 5000 ROSEMOUNT MODEL 8712U TRANSMITTER TABLE B-6. Brooks Model 5000 Flowtube...
Model 8712C/U/H Magnetic Flowmeter Transmitters Model 7400 Flowtube to Connect coil drive and electrode cables as shown in Figure B-7. Model 8712U Transmitter FIGURE B-7. Wiring Diagram for Brooks Flowtube Model 7400 and Rosemount Model 8712U BROOKS MODEL 7400 ROSEMOUNT MODEL 8712U TRANSMITTER TABLE B-7.
Connect coil drive and electrode cables as shown in Figure B-8. FLOWTUBES Endress and Hauser Flowtube to Model 8712U Transmitter FIGURE B-8. Wiring Diagram for Endress and Hauser Flowtubes ROSEMOUNT MODEL 8712U TRANSMITTER ENDRESS AND HAUSER FLOWTUBES Electrodes Coils Fuse TABLE B-8.
Model 8712C/U/H Magnetic Flowmeter Transmitters FISCHER AND PORTER Connect coil drive and electrode cables as shown in Figure B-9. FLOWTUBES Model 10D1418 Flowtube to Model 8712U Transmitter FIGURE B-9. Wiring Diagram for Fischer and Porter Flowtube Model 10D1418 and Rosemount...
Model 10D1419 Flowtube to Connect coil drive and electrode cables as shown in Figure B-10. Model 8712U Transmitter FIGURE B-10. Wiring Diagram for Fischer and Porter Flowtube Model 10D1419 and Rosemount Model 8712U ROSEMOUNT MODEL 8712U TRANSMITTER Electrode Connections Coil Connections TABLE B-10.
Model 8712C/U/H Magnetic Flowmeter Transmitters Model 10D1430 Flowtube Connect coil drive and electrode cables as shown in Figure B-11. (Remote) to Model 8712U Transmitter FIGURE B-11. Wiring Diagram for Fischer and Porter Flowtube Model 10D1430 (Remote) and Rosemount Model 8712U...
Connect coil drive and electrode cables as shown in Figure B-12. (Integral) to Model 8712U Transmitter FIGURE B-12. Wiring Diagram for Fischer and Porter Flowtube Model 10D1430 (Integral) and Rosemount Model 8712U ROSEMOUNT MODEL 8712U TRANSMITTER Electrode Connections To L2...
Model 8712C/U/H Magnetic Flowmeter Transmitters Model 10D1465 and Connect coil drive and electrode cables as shown in Figure B-13. Model 10D1475 Flowtubes (Integral) to Model 8712U Transmitter FIGURE B-13. Wiring Diagram for Fischer and Porter Flowtube Model 10D1465 and Model 10D1475...
Fischer and Porter Connect coil drive and electrode cables as shown in Figure B-14. Flowtube to Model 8712U Transmitter FIGURE B-14. Generic Wiring Diagram for Fischer and Porter Flowtubes ROSEMOUNT MODEL 8712U TRANSMITTER FISCHER AND PORTER FLOWTUBES Electrodes Chassis Ground...
Model 8712C/U/H Magnetic Flowmeter Transmitters FOXBORO FLOWTUBES Connect coil drive and electrode cables as shown in Figure B-15. Series 1800 Flowtube to Model 8712U Transmitter FIGURE B-15. Wiring Diagram for Foxboro Series 1800 and Rosemount Model 8712U FOXBORO SERIES ROSEMOUNT MODEL...
Connect coil drive and electrode cables as shown in Figure B-16. Flowtube to Model 8712U Transmitter FIGURE B-16. Wiring Diagram for Foxboro Series 1800 (Version 2) and Rosemount Model 8712U ROSEMOUNT MODEL FOXBORO SERIES 1800 8712U TRANSMITTER FLOWTUBE (VERSION 2)
Model 8712C/U/H Magnetic Flowmeter Transmitters Series 2800 Flowtube to Connect coil drive and electrode cables as shown in Figure B-17. Model 8712U Transmitter FIGURE B-17. Wiring Diagram for Foxboro Series 2800 and Rosemount Model 8712U FOXBORO SERIES 2800 ROSEMOUNT MODEL...
Wiring Diagrams Foxboro Flowtube to Connect coil drive and electrode cables as shown in Figure B-18. Model 8712U Transmitter FIGURE B-18. Generic Wiring Diagram for Foxboro Flowtubes ROSEMOUNT MODEL 8712U TRANSMITTER FOXBORO FLOWTUBE White Electrodes Black Any Shield Ground Coils Fuse TABLE B-18.
Model 8712C/U/H Magnetic Flowmeter Transmitters KENT VERIFLUX VTC Connect coil drive and electrode cables as shown in Figure B-19. FLOWTUBE Veriflux VTC Flowtube to Model 8712U Transmitter FIGURE B-19. Wiring Diagram for Kent Veriflux VTC Flowtube and Rosemount Model 8712U...
Wiring Diagrams KENT FLOWTUBES Connect coil drive and electrode cables as shown in Figure B-20. Kent Flowtube to Model 8712U Transmitter FIGURE B-20. Generic Wiring Diagram for Kent Flowtubes ROSEMOUNT MODEL 8712U TRANSMITTER KENT FLOWTUBES SIG2 Electrodes SIG1 SCR OUT...
Model 8712C/U/H Magnetic Flowmeter Transmitters KROHNE FLOWTUBES Connect coil drive and electrode cables as shown in Figure B-21. Krohne Flowtube to Model 8712U Transmitter FIGURE B-21. Generic Wiring Diagram for Krohne Flowtubes ROSEMOUNT MODEL 8712U TRANSMITTER KROHNE FLOWTUBES Electrodes Electrode Shield...
Connect coil drive and electrode cables as shown in Figure B-22. Series 1100 Flowtube to Model 8712U Transmitter FIGURE B-22. Wiring Diagram for Taylor Series 1100 Flowtubes and Rosemount Model 8712U TAYLOR SERIES 1100 ROSEMOUNT MODEL FLOWTUBE 8712U TRANSMITTER Electrode Connections...
Model 8712C/U/H Magnetic Flowmeter Transmitters Taylor Flowtube to Connect coil drive and electrode cables as shown in Figure B-23. Model 8712U Transmitter FIGURE B-23. Generic Wiring Diagram for Taylor Flowtubes ROSEMOUNT MODEL 8712U TRANSMITTER TAYLOR FLOWTUBE Electrodes S1 and S2...
Model 8712C/U/H Magnetic Flowmeter Transmitters YOKOGAWA FLOWTUBES Connect coil drive and electrode cables as shown in Figure B-25. Yokogawa Flowtube to Model 8712U Transmitter FIGURE B-25. Generic Wiring Diagram for Yokogawa Flowtubes ROSEMOUNT MODEL 8712U TRANSMITTER YOKOGAWA FLOWTUBES Electrodes Chassis Ground...
Wiring Diagrams GENERIC MANUFACTURER FLOWTUBES Generic Manufacturer Flowtube to Model 8712U Transmitter Identify the Terminals First check the flowtube manufacturer’s manual to identify the appropriate terminals. Otherwise, perform the following procedure. Identify coil and electrode terminals 1. Select a terminal and touch an ohmmeter probe to it. 2.
Page 106
Model 8712C/U/H Magnetic Flowmeter Transmitters B-28...
Need help?
Do you have a question about the 8712C and is the answer not in the manual?
Questions and answers