Voltage Limitations; Electrical Data -Without Powered Convenience Outlet; Electrical Data -With Powered Convenience Outlet; Electric Heat Correction Factors - York SUNLINE 2000 Installation Manual

Single package heat pump
Hide thumbs Also See for SUNLINE 2000:
Table of Contents

Advertisement

TABLE 7: VOLTAGE LIMITATIONS
POWER SUPPLY
380/415-3-50
TABLE 8: ELECTRICAL DATA -WITHOUT POWERED CONVENIENCE OUTLET
COMPRESSORS
MODEL
VOLTAGE
RLA
TONNAGE
EACH
380
9.6
BQ240
415
9.6
Note 1: Maximum HACR breaker of the same amp size is acceptable.
Note 2: Only 18kW of the 36 or 54kW, or only 36kW of the 72kW electric heat can be simultaneously energized with the mechanical
heating. The full heater kW operates only if both compressors are locked out.
TABLE 9: ELECTRICAL DATA -WITH POWERED CONVENIENCE OUTLET
COMPRESSORS
MODEL
VOLTAGE
RLA
TONNAGE
EACH
380
9.6
BQ240
415
9.6
Note 1: Maximum HACR breaker of the same amp size is acceptable.
Note 2: Only 18kW of the 36 or 54kW, or only 36kW of the 72kW electric heat can be simultaneously energized with the mechanical
heating. The full heater kW operates only if both compressors are locked out.
TABLE 10: ELECTRIC HEAT CORRECTION FACTORS
NOMINAL VOLTAGE
380
415
18
VOLTAGE
MIN.
342
OD FAN
BLOWER
MOTORS
LRA
MOTOR
FLA EACH
EACH
FLA
66
2.1
11.7
66
2.1
11.7
OD FAN
BLOWER
MOTORS
LRA
MOTOR
FLA EACH
EACH
FLA
66
2.1
11.7
66
2.1
11.7
VOLTAGE
KW CAP. MULTIPLIER
380
0.627
415
0.75
MAX.
456
HEATER OPTION
ID
CONV
OUTLET
MODEL KW
AMPS
-
0.0
E18
11.3
0.0
E36
22.6
E54
33.8
E72
45.1
-
0.0
E18
13.5
0.0
E36
26.9
E54
40.4
E72
53.8
HEATER OPTION
ID
CONV
OUTLET
MODEL KW
AMPS
-
0.0
E18
11.3
6.3
E36
22.6
E54
33.8
E72
45.1
-
0.0
E18
13.5
6.3
E36
26.9
E54
40.4
E72
53.8
66396-YIM-C-1004
MIN.
CIRCUIT
AMPACITY
2
STAGES AMPS
(AMPS)
-
-
57.2
1
17.1
78.7
2
34.3
78.7
2
51.4
78.8
2
68.6
100.3
-
-
57.2
1
18.7
80.7
2
37.4
80.7
2
56.2
84.9
2
74.9
104.0
MIN.
CIRCUIT
AMPACITY
2
STAGES AMPS
(AMPS)
-
-
63.5
1
17.1
85.0
2
34.3
85.0
2
51.4
86.7
2
68.6
108.2
-
-
63.5
1
18.7
87.0
2
37.4
87.0
2
56.2
92.8
2
74.9
110.3
Unitary Products Group
MAX.
FUSE/
1
BRKR
SIZE
(AMPS)
60
80
80
80
110
60
90
90
90
110
MAX.
FUSE/
1
BRKR
SIZE
(AMPS)
70
90
90
90
110
70
90
90
100
125

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Bq 240