Description Of Table 1 Interlock; I/O Terminals; Current Control - Ransburg MICROPAK A11789 Service Manual

Table of Contents

Advertisement

MicroPak Controller - Installation
Figure 5:
Figure 5:
Stripping of I/O Cable(s)
Stripping of I/O Cable(s)
Figure 5:
Figure 5:
Figure 5:
Stripping of I/O Cable(s)
Stripping of I/O Cable(s)
Stripping of I/O Cable(s)
DESCRIPTION OF TABLE
DESCRIPTION OF TABLE
DESCRIPTION OF TABLE
DESCRIPTION OF TABLE
DESCRIPTION OF TABLE
1 INTERLOCK AND I/O
1 INTERLOCK AND I/O
1 INTERLOCK AND I/O
1 INTERLOCK AND I/O
1 INTERLOCK AND I/O
TERMINALS
TERMINALS
TERMINALS
TERMINALS
TERMINALS
Input T
Input Terminals
Input T
erminals
erminals
erminals
Input T
Input T
erminals
kV Setpoint (0-10VDC)
kV Setpoint (0-10VDC)
kV Setpoint (0-10VDC)
kV Setpoint (0-10VDC)
kV Setpoint (0-10VDC)
0 to 10 VDC remote analog signal input that controls
applicator output from 0 to 100 kV DC when high
voltage is enabled. This input is active when the
MicroPak local/remote switch is in the remote
position. Otherwise control is from the kV adjust
knob on the front of the MicroPak. In either mode,
the kV setpoint can be viewed by pushing and
holding the View/Change Setpoint switch (see
Figure 8) on the front of the MicroPak.
Voltage Control Over-Current
Voltage Control Over-Current
Voltage Control Over-Current
Voltage Control Over-Current
Voltage Control Over-Current
Setpoint (0-10VDC)
Setpoint (0-10VDC)
Setpoint (0-10VDC)
Setpoint (0-10VDC)
Setpoint (0-10VDC)
0 to 10VDC remote analog signal input that sets the
over-current point when high voltage is enabled. If
the current goes above this setpoint an over-
current fault will occur. This input is active when
the MicroPak local/remote switch is in the remote
position and dipswitch SW3-1 on the MicroPak
process board (see Figure 6A) is set to the ON
position. The range of the over-current setpoint in
this mode is 0 to 10VDC. The microamps are
limited to 240 for voltage above 10VDC.
For example: 3.30VDC = 85 microamps
If the local/remote switch is in the remote position
and dipswitch SW3-1 is OFF, then potentiometer
R21 on the top of the MicroPak process board (see
1 1 1 1 1 1 1 1 1 1
Figure 6A) will control the over-current setpoint.
This mode is convenient if it is desired to supply an
analog input signal for the kV setpoint but not for the
over-current setpoint.
Finally, if the local/remote switch is in the local
position, the over-current setpoint is controlled by
the μA adjust knob on the front of the MicroPak.
If any of the modes, the over-current setpoint can
be viewed by pushing and holding the View/Change
Setpoint switch (see Figure 8) on the front of the
MicroPak.

CURRENT CONTROL

CURRENT CONTROL
CURRENT CONTROL
CURRENT CONTROL
CURRENT CONTROL
Over-Current Setpoint (90-10VDC)
Over-Current Setpoint (90-10VDC)
Over-Current Setpoint (90-10VDC)
Over-Current Setpoint (90-10VDC)
Over-Current Setpoint (90-10VDC)
0 to 10VDC remote analog signal input that sets the
desired current. The current control unit will limit
the maximum current to this setpoint. If the current
goes over this setpoint, then a fault will occur.
If the voltage setpoint is set low, then the unit will
only allow enough current to achieve the kV setpoint.
It may be simpler to think of the kV setpoint as the
controlling variable when the kV setpoint is achieved
before the current setpoint.
The range of current is 0 to 240 microamps with 0
to 10VDC analog input.
For example: 10VDC = 240 microamps
3.30VDC = 85 microamps
High Voltage Reset (24VDC)
High Voltage Reset (24VDC)
High Voltage Reset (24VDC)
High Voltage Reset (24VDC)
High Voltage Reset (24VDC)
24VDC remote input signal that allows remote
reset of fault conditions. When a fault occurs, a
momentary supply of 24VDC to this terminal will
reset the fault. Faults can also be reset by moving
the kV ON/OFF toggle switch on the front of the
MicroPak to the OFF position and back to the ON
position. This input can also be used to remove the
MicroPak from ready mode.
High Voltage On (24VDC)
High Voltage On (24VDC)
High Voltage On (24VDC)
High Voltage On (24VDC)
High Voltage On (24VDC)
Remote input signal that enables high voltage.
When 24VDC is supplied to this terminal, high
voltage will be enabled. This input mode is active
in either local or remote mode when dipswitch
CP-06-01

Advertisement

Table of Contents
loading

Table of Contents