Generator protection REG650
Product version: 1.3
Table 76. RI and RD type inverse time characteristics
Function
RI type inverse characteristic
1
=
×
t
k
0.236
-
0.339
I
EQUATION1137-SMALL V1 EN
I = I
/I
measured
set
RD type logarithmic inverse characteristic
æ
ö
I
-
ç
×
÷
5.8
1.35
In
=
t
è
ø
k
EQUATION1138-SMALL V1 EN
I = I
/I
measured
set
Table 77. Inverse time characteristics for overvoltage protection
Function
Type A curve:
k
=
t
æ
ö
-
>
U
U
ç
÷
è
ø
>
U
EQUATION1436-SMALL V1 EN
U> = U
set
U = U
measured
Type B curve:
×
k
480
=
t
2.0
æ
ö
-
>
U
U
ç
×
-
÷
32
0.5
è
ø
>
U
EQUATION1437-SMALL V1 EN
Type C curve:
×
k
480
=
t
3.0
æ
ö
-
>
U
U
ç
×
-
÷
32
0.5
è
ø
>
U
EQUATION1438-SMALL V1 EN
ABB
Range or value
k = (0.05-999) in steps of 0.01
k = (0.05-999) in steps of 0.01
Range or value
k = (0.05-1.10) in steps of 0.01
k = (0.05-1.10) in steps of 0.01
-
0.035
k = (0.05-1.10) in steps of 0.01
-
0.035
1MRK 502 050-BEN B
Accuracy
Accuracy
±5% +60 ms
61