Table 18. Electromagnetic compatibility tests, continued
Description
Voltage dips and interruptions on AC power
supply
Electromagnetic emission tests
• Conducted, RF-emission (mains terminal)
0.15...0.50 MHz
0.5...30 MHz
• Radiated RF-emission, IEC
30...230 MHz
230...1000 MHz
Table 19. Insulation tests
Description
Dielectric tests:
• Test voltage
Impulse voltage test:
• Test voltage
Insulation resistance measurements
• Isolation resistance
Protective bonding resistance
• Resistance
ABB
Type test value
Dips:
40% 10/12 cycles at 50/60 Hz
70% 25/30 cycles at 50/60 Hz
Interruptions:
0–50 ms: No restart
0...∞ s: Correct behaviour at power down
< 79 dB(µV) quasi peak
< 66 dB(µV) average
< 73 dB(µV) quasi peak
< 60 dB(µV) average
< 40 dB(µV/m) quasi peak, measured at 10 m
distance
< 47 dB(µV/m) quasi peak, measured at 10 m
distance
Type test value
2 kV, 50 Hz, 1 min
1 kV, 50 Hz, 1 min, communication
5 kV, unipolar impulses, waveform 1.2/50 μs,
source energy 0.5 J
1 kV, unipolar impulses, waveform 1.2/50 μs,
source energy 0.5 J, communication
>100 MΏ, 500 V DC
<0.1 Ώ (60 s)
1MRK 502 050-BEN B
Reference
IEC 60255–11
IEC 61000–4–11
EN 55011, class A
IEC 60255-25
ANSI C63.4, FCC
Reference
IEC 60255-5
ANSI C37.90-2005
IEC 60255-5
ANSI C37.90-2005
IEC 60255-5
ANSI C37.90-2005
IEC 60255-27