1) Input for independent non-directional OC and overload functions. It can be used for different purposes (e.g. OC protection
for either Auxiliary trafo or Excitation trafo or Step-up transformer HV side)
2) Input for independent non-directional EF function. It can be used for different purposes (e.g. as stator EF protection or turn-to-turn protection for generators with split winding or even HV side
EF protection). Alternatively it can be used for High-Impedance REF protection.
3) Input for independent directional (sensitive) EF function. It can be used for different purposes.
(e.g. as rotor EF with RXTTE4 or stator EF for generators operating in parallel)
IEC10000299 V3 EN
Figure 1.
Generator protection IED including generator differential protection (B01)
4
200/1
J
0.11 0.11
/
/
kV
3
3
Y
59N
3Uo>
ROV2 PTOV
1)
51
3I>
A, B, C or D
OC4 PTOC
0.11 0.11
/
/
kV
3
3
Y
59N
3Uo>
Y
ROV2 PTOV
52PD
PD
CC RPLD
3)
Rotor EF protection 64R
U
67N
IN>
SDE PSDE
I
29MVA
11kV
150rpm
46
I2>
NS2 PTOC
11
/ 0.11
kV
3
51N
H
J, G or H
EF4 PTOC
2)
¤) Requires dedicated CT cores, external resistor and metrosil for correct operation