ABB REG650 Product Manual page 36

Generator protection relion 650 series
Hide thumbs Also See for REG650:
Table of Contents

Advertisement

Generator protection REG650
Product version: 1.3
Type tests according to standards
Table 18. Electromagnetic compatibility tests
Description
100 kHz and 1 MHz burst disturbance test
• Common mode
• Differential mode
Electrostatic discharge test
• Contact discharge
• Air discharge
Radio frequency interference tests
• Conducted, common mode
• Radiated, amplitude-modulated
Fast transient disturbance tests
• Communication ports
• Other ports
Surge immunity test
• Communication
• Other ports
• Power supply
Power frequency (50 Hz) magnetic field
• 3 s
• Continuous
Pulse magnetic field immunity test
Damped oscillatory magnetic field
Power frequency immunity test
• Common mode
• Differential mode
Voltage dips and short interruptionsc on DC
power supply
36
Type test value
2.5 kV
2.5 kV
8 kV
15 kV
10 V (emf), f=150 kHz...80 MHz
20 V/m (rms), f=80...1000 MHz and f=1.4...2.7
GHz
4 kV
4 kV
1 kV line-to-earth
2 kV line-to-earth, 1 kV line-to-line
4 kV line-to-earth, 2 kV line-to-line
1000 A/m
100 A/m
1000A/m
100A/m, 100 kHz and 1MHz
300 V rms
150 V rms
Dips:
40%/200 ms
70%/500 ms
Interruptions:
0-50 ms: No restart
0...∞ s : Correct behaviour at power down
1MRK 502 050-BEN B
Reference
IEC 61000-4-18, level 3
IEC 60255-22-1
ANSI C37.90.1-2012
IEC 61000-4-2, level 4
IEC 60255-22-2
ANSI C37.90.3-2001
IEC 61000-4-6 , level 3
IEC 60255-22-6
IEC 61000-4-3, level 3
IEC 60255-22-3
ANSI C37.90.2-2004
IEC 61000-4-4
IEC 60255-22-4, class A
ANSI C37.90.1-2012
IEC 61000-4-5
IEC 60255-22-5
IEC 61000-4-8, level 5
IEC 61000–4–9, level 5
IEC 6100–4–10, level 5
IEC 60255-22-7, class A
IEC 61000-4-16
IEC 60255-11
IEC 61000-4-11