ABB REG650 Product Manual page 35

Generator protection relion 650 series
Hide thumbs Also See for REG650:
Table of Contents

Advertisement

Generator protection REG650
Product version: 1.3
Table 16. Environmental conditions
Description
Operating temperature range
Short-time service temperature range
Relative humidity
Atmospheric pressure
Altitude
Transport and storage temperature range
Table 17. Environmental tests
Description
Cold tests
operation
storage
Dry heat tests
operation
storage
Damp heat tests
steady state
cyclic
ABB
Type test value
96 h at -25ºC
16 h at -40ºC
96 h at -40ºC
16 h at +70ºC
96 h at +85ºC
240 h at +40ºC
humidity 93%
6 cycles at +25 to +55ºC
humidity 93...95%
Value
-25...+55ºC (continuous)
-40...+70ºC (<16h)
Note: Degradation in MTBF and HMI performance outside the
temperature range of -25...+55ºC
<93%, non-condensing
86...106 kPa
up to 2000 m
-40...+85ºC
Reference
IEC 60068-2-1/ANSI C37.90-2005 (chapter 4)
IEC 60068-2-2/ANSI C37.90-2005 (chapter 4)
IEC 60068-2-78
IEC 60068-2-30
1MRK 502 050-BEN B
35

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Reb650

Table of Contents