PS 3 Auxiliary function parameter
Parameter Description
XDZ
Dead zone or offset (refer to the above explanation)
MAX
the value to start Limiter cooling/direct acting
MIN
the value to start Limiter heating/reverse acting
XP-h / -r
the P-band in Limiter heating/reverse acting
XP-c / -d
the P-band in Limiter cooling/direct acting
TN-h / -r
integrating time heating/reverse acting
TN-c / -d
integrating time cooling/direct acting
COMP start point heating/reverse acting
COMP end point heating/reverse acting
adjustment in heating/reverse acting
COMP start point cooling/direct acting
COMP end point cooling/direct acting
adjustment in cooling/direct acting
MAX
maximum of virtual setpoint
MIN
minimum of virtual setpoint
XPh1 / r1
1st heating/reverse acting P-band in Cascade
XPc1 / d1
1st cooling/direct acting P-band in Cascade
WIN
As X2 < WIN, Q1 is reverse acting
SUM
As X2 > SUM, Q1 is direct acting
Time elapsed to allow next winter/summer changeover (Q1
T
only)
There are no PS3 auxiliary function parameters for applications #8 and #9.

Operating Modes

The controller has three operating buttons for the following functions:
SELECT
The SELECT
The
Time-out
For setpoint adjustment in Normal mode, the controller will exit the setting after 20 seconds automatically. However, for setpoint
adjustment in Service (PS) mode, there is no time limit. The controller remains on the PS mode until the user completes the
whole process.
Note
Only those parameters that apply to a particular program appear on the display or in the sequence in programming.
For example, if the second analogue input is not used, X2 values and selections will not appear.
A software tool (S3341A031EN0) for controller application selection and parameter adjustment is available. It is a user-friendly Windows
95 (or above) based software tool which provides you a printout of the controller settings.
Parameters can be hidden from display if desired by using the software tool.
Siemens Building Technologies
button is used to enter or save the value adjustment.
operating buttons are used for viewing and adjusting parameters.
O3341(RWD32) V14.doc
Auxiliary number:
#x1
#x2
#x3
#x4
REM
LIM
LIM
COMP
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
O3341A031En2
8-Jun-01
#x5
#x6
#x7
CAS
WIN/SUM
WIN/SUM
x
x
x
x
x
x
x
x
x
x
Page 5
®

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Rwd82

Table of Contents