Siemens RWD32 Installation And Commissioning Manual page 7

Table of Contents

Advertisement

Service (PS) Mode screen sequence
Press
both buttons and hold them for 5 sec to enter the Service Mode.
Press
for viewing the next page and parameter OR to increase value.
Press
for viewing the previous page and parameter OR to decrease value.
Press
to enter the PS page OR edit and save the value when the page appears with the logo
On entering service (PS) mode, PS4 appears first.
For initial setup, proceed directly to PS1 and enter your desired application number first.
PS1 will already be opened if power has never been connected to new controller.(Refer below *)
PS2 to PS4 parameters may need to be adjusted for service/commissioning purposes.
X1
Q1
Q2
Siemens Building Technologies
C
Main loop
- Switching differential
- Switching delay time
- Dependent loop Q1 on point
- P band for 3-point control
- I action time for 3-point control
- 3-point actuator cycle time
- Day/night setpoint
- Winter/summer setpoint
Auxiliary loop
- Max/Min limiter
- Proportion band
- Integral time
- Compensation shifts start/end point
- Winter/Summer changeover temp.
and time delay
Define unit, X1 & X2
- Define the unit as
or no unit
- Sensor type
- Sensing range
- Calibration offset
Application no.
- Application no. selection
O3341(RWD32) V14.doc
- Day/night setpoint
- Winter/summer setpoint
o
C,
o
F, %
(wait 2 second)
O3341A031En2
New controller application
and setpoint sequence
Normal programming
* New controller
8-Jun-01
Page 7