Siemens FDS229-A Technical Manual page 38

Fds229 series. alarm sounder with supplementary optical indication
Hide thumbs Also See for FDS229-A:
Table of Contents

Advertisement

8
Specifications
Technical data
External alarm indicators
Function
Connections
38
Building Technologies
Fire Safety
Number of external alarm indicators that
can be connected
Voltage
Current
Length of line
Number of sounds
Number of optical indicator patterns
Activation levels
Sound intensity
Light intensity at 32 VDC
(depending on viewing angle
-30° ... +30°):
FDS229-R: Red hood
FDS229-A: Orange hood
Detector line:
Design
External alarm indicators:
Design
MC link:
Design
2
DC 10...17 V
9...15 mA
Max. 30 m with unshielded cables
(recommended), or when the shielding is
connected to the positive pole of the AI on
the detector base
Max. 5 m, if the shielding is connected to
earth
11
1
2
Depending on the set tone; see chapter
'Configuration' for details
1.0 ... 2.1 cd
Depending on the viewing angle, see 'Technical
data annex', sub-chapter 'FDS229-R, red'
0.9 ... 1.8 cd
Depending on the viewing angle, see 'Technical
data annex', sub-chapter 'FDS229-A, orange'
Plug-type connection
Plug-type connection
Proximity interface
010095_j_en_--