Preparing for installation
Specifications of the non-pump models
Power supply
Cooling (Rated)
Capacity
Heating (Rated)
Cooling (Rated)
Power
consumption
Heating (Rated)
Cooling (Rated)
Operating
current
Heating (Rated)
Refrigerant
Charging amount
(Cooling/Heating)
Water
Maximum operating
side heat
exchanger
Inlet·Outlet connected
Minimum water quantity
Net weight
Net dimension
Remote control
Water outlet
Cooling (If using brine)
temperature
range
Surrounding
temperature
range
MCA
MFA
1) Standard for rated cooling capacity: chilled water inlet/outlet temperature 12/7 °C, outdoor 35 °C DB, 24 °C WB
2) Standard for rated heating capacity: heating water inlet/outlet temperature 40/45 °C, outdoor 7 °C DB, 6 °C WB
3) When using brine, maintain the concentration according to temperature. (Refer to page 76.)
8
English
Model
kW
kW
kW
kW
A
A
Type
kg
Type
Flow rate
LPM
MPa
pressure
Head loss
kPa
A
pipe size
L
kg
W X H X D
mm
°C
Heating
°C
Cooling
°C
Heating
°C
A
A
AG042KSVANH
AG056KSVANH
3 Phase 4 Wires 380 ~ 415 V, 50/60 Hz
42
42
12.35
18.67
11.83
17.50
19.6
29.6
18.8
27.8
R-410A
R-410A
18
Plate type heat exchanger
120/120
160/160
1.0
60
100
40
294
392
446
446
1795 X 1695 X
1795 X 1695 X
765
765
Module Control
5 ~ 25 (-10 ~ 25)
5 ~ 25 (-10 ~ 25)
25 ~ 55
25 ~ 55
-15 ~ 48
-15 ~ 48
-25 ~ 43
-25 ~ 43
32
40
AG070KSVANH
56
65
56
69.5
26.0
24.39
41.2
38.7
R-410A
18
18
186/200
1.0
1.0
120
40
50
490
465
1795 X 1695 X
765
5 ~ 25 (-10 ~ 25)
25 ~ 55
-15 ~ 48
-25 ~ 43
46
58
60
75