Fixing the power cable

CAUTION
Do not let the power cable come into contact with
the pipes inside the DVM CHILLER. If the power
supply cable touches the pipes, the vibration of
the compressor is transferred to the pipes and can
damage the power supply cables or pipes, creating
the danger of fire or explosion.
Make sure that the place where the sheath of power
supply cable is removed is inside the power supply
box. If it is impossible, you should connect the
protection tube for power cable to the power supply
box.
After arranging the power cable into the power
supply box, tighten the cover.
3 Phase
4 Wires
380 - 415 V
ELCB or
MCCB+ELB
Connecting ring terminal of 3 phase
cable
1 Cut the power cable to an appropriate length and
connect it with the solderless terminal.
2 After connecting the power cable to the terminal as
seen in the illustration, fix it with cable tie.
3 Fix the housing, which has an insulator, to the
terminal board.
Communication
cable

Fixing the ground cable

Connect the ground cable to the grounding hole inside
the power supply box.
Grounding