Controlled Outgoing Circuit For Auxiliary Equipment 400 V 3 Ac Or 460/480 V 3 Ac (Option N32); Table 3-4 T-X30 Terminal Strip For Connecting Auxiliary Equipment; Table 3-5 Outgoing Circuit For Auxiliary Equipment (Option N32); Table 3-6 T-X30 Terminal Strip For Connecting Auxiliary Equipment - Siemens GH180 Operating Instructions Manual

Medium-voltage drive sinamics perfect harmony
Hide thumbs Also See for GH180:
Table of Contents

Advertisement

Table 3-4
T-X30 terminal strip for connecting auxiliary equipment
Supplying the auxiliary voltage
Terminal
.T–X30:6
.T–X30:7
.T–X30:8
Note
The infeed required for the drive power supply must be provided externally.
For further details see: Interconnection diagram
3.1.6.35
Controlled outgoing circuit for auxiliary equipment 400 V 3 AC or 460/480 V 3 AC (option
N32)
This option provides a controlled output that is protected via the motor circuit breaker and is
used for operating external auxiliary equipment (e.g. separately-driven fan for motor, pumps,
and oil supplies).
The contactor is energized by means of an ON command on the converter. The OFF command
deactivates the contactor.
Table 3-5
Controlled outgoing circuit for auxiliary equipment Setting range of the motor circuit breaker
400 V 3 AC, 50 Hz, max. 11 KW
460/480 V 3 AC, 60 Hz, max. 12.7 KW
Table 3-6
T-X30 terminal strip for connecting auxiliary equipment
Supplying the auxiliary voltage
Terminal
.T–X30:6
.T–X30:7
.T–X30:8
Note
The infeed required for the drive power supply must be provided externally.
SINAMICS PERFECT HARMONY GH180 6SR41 manufactured in NMA Nuernberg, Germany
Operating Instructions Rev.201706301306
Outgoing circuit for auxiliary equip‐
Connector
Terminal
L1
.T–X30:3
L2
.T–X30:4
L3
.T–X30:5
Outgoing circuit for auxiliary equipment (option N32)
Outgoing circuit for auxiliary equip‐
Connector
Terminal
L1
.T–X30:3
L2
.T–X30:4
L3
.T–X30:5
ment
Connector
L1
L2
L3
Cos phi = 0.8; 18 A to 25 A
Cos phi = 0.8; 18 A to 25 A
ment
Connector
L1
L2
L3
3.1 Cabinet Details
Feedback: auxiliary equipment ON
Terminal
Connector
.T–X30:1
Relay contact
max. 60 V DC
.T–X30:2
Feedback: auxiliary equipment ON
Terminal
Connector
.T–X30:1
Relay contact
max. 60 V DC
.T–X30:2
Description
53