Procom ECON-F Installation Manual page 11

Table of Contents

Advertisement

Fuel Warn
25 %
Level #
Fuel Warn
10 Sec
Delay #
Fuel Trip
15 %
Level #
Fuel Trip
10 Sec
Delay #
LLOP Trip
0.4-
Level
8.5Kg/cm
LLOP
1-999
Trip Delay
Sec
HWT trip
40-250 C The maximum coolant
level
Operating Instructions
Monitoring value of fuel level below
which fuel level warning is
generated.
Monitoring time of fuel level after
which fuel level warning is
generated.
Monitoring value of fuel level below
which fuel level trip is generated.
Monitoring time of fuel level after
which fuel level trip is generated.
The minimum lubricant oil pressure
2
on which the engine is allowed to
operate. A drop of pressure below the
set limit shall trigger a fault condition
thereby stopping the engine
Duration for which the low lubricant
oil pressure can be tolerated.
o
temperature up to which the engine
is allowed to operate.
Disable*
11-80 %
1-999Sec
10-80 %
1-999 Sec
2
1.0Kg/cm
5
o
95 C
Page - 10

Hide quick links:

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the ECON-F and is the answer not in the manual?

Questions and answers

Table of Contents