Diagnostics Alarms - Siemens SIMATIC ET 200AL Manual

Communication module cm 4xio-link 4xm12
Hide thumbs Also See for SIMATIC ET 200AL:
Table of Contents

Advertisement

LEDs Qn
Valid for IO-Link port in SIO mode.
Table 5- 4
Q1, Q2, Q3, and Q4 LEDs
5.2

Diagnostics alarms

For each diagnostic event, a diagnostics alarm is issued and the DIAG LED flashes red on
the communication module. You can read out the diagnostics alarms, for example, in the
diagnostics buffer of the CPU. You can evaluate the error codes with the user program.
Table 5- 5
Error types
Diagnostics
Error
alarm
code
Short-circuit
1
H
Undervoltage
2
H
Overvoltage
3
H
Overtemperature 5
H
Wire break
6
H
Overflow
7
H
Underflow
8
H
Error
9
H
Communication module CM 4xIO-Link 4xM12(6ES7147-5JD00-0BA0)
Manual, 10/2017, A5E32352322-AE
Status displays of the Q1, Q2, Q3, and Q4 LEDs
Meaning
Process signal = 0 in SIO mode, deactivated or in IO-Link mode
Off
Process signal = 1 in SIO mode
On
Meaning (IO-Link error code)
Short-circuit at the process cables on the IO-Link device (1804
Short-circuit on IO device (7710
Supply voltage too low (5111
Supply voltage too high (5110
Temperature exceeded on master (1805
Temperature exceeded on device (4000
No IO-Link device connected
There is a break on the signal line to the IO-Link device
IO-Link device cannot communicate due to a different error
(1800
)
H
Process tag range exceeded (8C10
Measuring range exceeded (8C20
Process tag range too low (8C30
All IO-Link error codes which are not listed here are mapped to
this PROFIBUS DP error
)
H
, 5112
)
H
H
)
H
)
H
, 4210
)
H
H
)
H
)
H
)
H
Diagnostics alarms
5.2 Diagnostics alarms
IO-Link
IO-Link
master
device
X
)
H
X
X
X
X
X
X
X
X
X
27