Functions; Reset Communication Module To Factory Settings - Siemens SIMATIC ET 200AL Manual

Communication module cm 4xio-link 4xm12
Hide thumbs Also See for SIMATIC ET 200AL:
Table of Contents

Advertisement

Product overview

2.3 Functions

2.3
Functions
IO-Link is a point-to-point connection between an IO-Link master and an IO-Link device. On
the IO-Link master, you can use IO-Link devices as well as conventional sensors/actuators
with unshielded standard cables using proven 3-wire technology. IO-Link is backward
compatible to conventional digital sensors or actuators. Switching status channel and data
channel are in proven 24 V DC technology.
Reference
For more information on the IO-Link system, please see the IO-Link system
(http://support.automation.siemens.com/WW/view/en/65949252) function manual.
2.4

Reset communication module to factory settings

Effects of resetting to the factory settings
Use the "Reset to factory settings" function to restore the parameter assignments of your
CM 4xIO-Link 4xM12 communication module made with S7-PCT to the factory state.
After a "Reset to factory settings", the parameters of the CM 4xIO-Link 4xM12
communication module are assigned as follows:
● The ports are in DI mode
● The ports are mapped to the relative addresses 0.0 ... 0.3
● The PortQualifier is disabled
● The I&M data 1 ... 3 are deleted
Note
The device parameters are deleted and the factory state is restored.
You should reset a removed CM 4xIO-Link 4xM12 communication module to the factory
settings before you place it in storage.
Procedure
To perform a "Reset to factory settings", proceed as described in the S7-PCT online help.
14
Communication module CM 4xIO-Link 4xM12(6ES7147-5JD00-0BA0)
Manual, 10/2017, A5E32352322-AE

Advertisement

Table of Contents
loading

Table of Contents