MODBUS COMMUNICATION

■ COMMUNICATION PARAMETERS
PARAMETER
Data Mode
Baud Rate
Bit Length
Node Address
Floating Point Data
Interface
■ FUNCTION CODES & SUPPORTED CODES
CODE
NAME
01
Read Coil Status
02
Read Input Status
03
Read Holding Registers
04
Read Input Registers
05
Force Single Coil
06
Preset Single Registers
07
Read Exception Status
08
Diagnostics
09
Program 484
10
Poll 484
11
Fetch Comm. Event Counter
12
Fetch Comm. Event Log
13
Program Controller
14
Poll Controller
15
Force Multiple Coils
16
Preset Multiple Registers
17
Report Slave ID
18
Program 884/M84
19
Reset Comm. Link
20
Read General Reference
21
Write General Reference
22
Mask Write 4X Register
23
Read/Write 4X Register
24
Read FIFO Queue
Parity
Stop Bit
X
Digital output from the slave
X
Status of digital inputs to the slave
X
General purpose register within the slave
X
Collected data from the field by the slave
X
Digital output from the slave
X
General purpose register within the slave
Fetch a status word and an event counter
A status word, an event counter, a message count and a field of event bytes
X
Digital output from the slave
X
General purpose register within the slave
Slave type / 'RUN' status
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: info@m-system.co.jp
SPECIFICATION
RTU
9600 / 19200 / 38400 (*) bps
None / Odd (*) / Even
8
1 (*) / 2
1 (*) to 15
N/A
RS-232-C / RS-485
EM-5661 Rev.6 P. 5 / 8