■ INPUT REGISTERS DESCRIPTION
(1) ANALOG INPUT IN % (30001 to 30016; 30001 to 30008 for J3)
Indicates analog input values in percentage for each channel (1 – 16; 1 – 8 for J3).
INPUT TYPE & RANGE
DC
Thermocouple
RTD
Potentiometer
(2) ANALOG INPUT IN ENGINEERING UNIT (30017 to 30048; 30017 to 30032 for J3)
Indicates analog input values in engineering unit for each channel (1 – 16; 1 – 8 for J3). The unit is specific to each input
type: °C for temperature, Volts for voltage, and % for potentiometer. The data are 32-bit floating values, which requires two
consecutive registers for one module.
(3) CHANNEL STATUS (30081 to 30096)
Indicates the current status of analog inputs (1 – 16; 1 – 8 for J3). The following list shows the names and descriptions of
each bit.
BIT
NAME
6
Input Overrange
7
ADC Error
12
Cold Junction Compensation SW
Others
Reserved
±20 V
±5 V
±1 V
±0.8 V
±0.2 V
±50 mV
±10 mV
0 – 100 Ω
0 – 500 Ω
0 – 1 kΩ
0 – 10 kΩ
DESCRIPTION
Indicates the designated analog input is in overrange, defined as one or
more of the following condition:
• ADC input value 0x0000 or 0xFFFF
• Burnout status for thermocouple, RTD and Potentiometer input
• Out of range defined in the temperature table (thermocouple and RTD)
• ADC error
0 : Normal
1 : Overrange
Indicates the status of ADC.
0 : Normal
1 : Error
Indicates whether the cold junction compensation is enabled or disabled,
for thermocouple input.
0 : Disable
1 : Enable
For system's use
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: info@m-system.co.jp
A/D DATA (Decimal)
±20000
±5000
±10000
±8000
±20000
±5000
±10000
Temperature
10
5
Temperature
10
5
±2000
EM-5661 Rev.6 P. 7 / 8