Combustion Characteristics; Chimney Connection Characteristics - ACV HeatMaster 201 Installation, Operation And Maintenance Instructions

Hide thumbs Also See for HeatMaster 201:
Table of Contents

Advertisement

EN
TECHNICAL CHARACTERISTICS

COMBUSTION CHARACTERISTICS

FR
Main Characteristics
max
Input (PCI)
min
NL
(80/60°C)
Output at 100%
(50/30°C)
(80/60°C)
Efficiency at 100%
(50/30°C)
ES
Efficiency at 30% load (EN677)
Combustion efficiency
at 100%
Max. output
IT
NOx (Class 5)
Min. output
Weighted
Max. output
CO
Min. output
DE
Max. output
CO
2
Min. output
20 mbar
Max gas flow rate
G20/G25
PL
25 mbar
Average
Temp of flue gases
Max.
Min.
RU
Average temp. of combus-
DHW mode
tion products
Mass flow rate* of flue
Nominal
gases
∆T = 45 K
Standby loss
∆T = 30 K
* Mass flow rate values were calculated for G20 with an air factor of 1.3.
en
18
HM201
G20/G25
kW
220.0
kW
58.4
kW
198.0
kW
%
91.0
%
%
94.0
%
91.5
mg/kWh
68.0
mg/kWh
45.0
mg/kWh
43.0
ppm
4
ppm
2
%CO
9.5
2
%CO
8.9
2
m³/h
25.4
m³/h
29.5
°C
150
°C
194
°C
92
°C
187
g/s
113
W
678
W
408

CHIMNEY CONNECTION CHARACTERISTICS

Main Characteristics
Air/flue pipe Ø
Parallel
Max. allowed flue pipe pressure
drop
Max recommended length (corresponding
length in meters of straight pipes)
Available connection types
FLUE PIPE CONNECTION TYPES
It is mandatory to use ACV flue systems to connect the appliance.
B23
: Connection to an exhaust duct that discharges the combustion products outside the room
where it is installed, with the combustion air being drawn directly from the boiler room.
B23P:
: Connection to a combustion product exhaust system designed to operate with positive pressure.
C53(x) : Connection to separate ducts for supplying combustion air and discharging combustion prod-
ucts; these ducts may end in zones with different pressure levels, but are not allowed to be
installed on opposite walls of the building.
It is mandatory to ventilate the boiler room. The high or low air vent opening dimensions
depend on the appliance power and the boiler room size. Refer to the local regulations in force.
C
53(x)
HeatMaster201: A1004320 - 664Y7500 • A
HM201
mm
250
Pa
130
12 m
B23 - B23P - C53(x)
B
23P
B
23