Quadra-Fire 5100I-GD-B User Manual page 15

5100-i act wood insert advanced combustion technology
Hide thumbs Also See for 5100I-GD-B:
Table of Contents

Advertisement

Masonry Chimney (Cont'd)
The Quadra-Fire 5100-I Insert conforms with the UL 18
and ULC S68 (Canada) in all respects, and is approved to
UL & ULC safety standards for installation and use within a
fireplace with a masonry chimney in accordance with NFPA
11 and CAN/CSA-B65-01.
Installation into fireplaces without a permit will
NOTE:
void the listing.
UL 1777 Insulated Stainless Steel
Liner or Other Approved Lining System
Follow Manufacturer's Instructions
on Insulation and Support
For Zero or Other Non-Code Clearances,
Follow Approved Liner Manufacturer's Specific
Insulation Requirements: Different Clearances
May Require Different Specifications
Masonry Chimney Must
Have Structural Integrity
UL 1777 Insulated Stainless Steel
Liner or Other Approved Lining System
Minimum 8 in. (203mm) Masonry
Thickness in Front of Smoke Chamber
Minimum Clearance in Accordance
Accordance with Insert
Figure 15.1
April 21, 2010
5100-I ACT WOOD INSERT
with Insert Listing
Floor Protection in
Listing
Combustible Floor
NOTE: In Canada, this fireplace insert must be installed
with a continuous chimney liner of a 6 inch (152mm) diam-
eter extending from the fireplace insert to the the top of the
chimney. The chimney liner must conform to the Class 
requirements of CAN/ULC-S65, Standard for Lining Sys-
tems for Existing Masonry or Factory-Built Chimneys and
Vents, or CAN/ULC-S60, Standard for Lining Systems
for New Masonry Chimneys.
Follow Manufacturer's
Instructions for Maximum
Liner Extension Above
Chimney
Maximum 30 Degrees
Offset in Chimney
Damper Plate Removed or
Fastened in Open Position
Seal with Non-Combustible Material
438-0380E
R
Page 15