3. SELECTING THE LOCATION FOR THE INDOOR UNIT

3-1. Required Minimum Space for Installation and Service.
Provide a check port on the piping side ceiling for repair and maintenance.
Install the indoor unit once the following conditions are satisfied and after receiving the customer approval.
1. The indoor unit must be within a maintenance space.
2. The indoor unit must be free from any obstacles in path of the air inlet and outlet, and must allow spreading of air
throughout the room.
Top view
(Unit:mm)
If the height from the floor to ceiling exceeds three meters, air flow distribution deteriorates and the effect is
decreased.
POSITION OF SUPENSION BOLT
A
B
(Unit:mm)
TYPE
A
S-36PN1E5
840 780 523
S-45PN1E5
S-50PN1E5
S-60PN1E5
1060 1000 523
S-71PN1E5
S-100PN1E5
S-125PN1E5
1260 1200 523
S-140PN1E5
Control box
Front view
Inspection hole
(600 x 600)
600
600
<Front>
B
C
D
E
64
650
64
650
64
650
Above 250cm
Apply a joint-canvas between the unit and duct to absorb unnecessary
vibration.
Install the unit leaning to a drainage hole side as a figure for easy water
drainage.
Drainage hole
Caution
Remove the absorber at air return
hole before installation.
Absorber
7
1~3mm
Fig.3-1
Fig.3-1.1