GE D30 Instruction Manual page 325

Line distance protection system
Hide thumbs Also See for D30:
Table of Contents

Advertisement

CHAPTER 5: SETTINGS
Table 5-13: Oscillography cycles/record example
Records
CT/VTs
3
1
3
1
16
1
16
1
32
1
32
1
3
2
3
2
16
2
— A new record automatically overwrites an older record when
TRIGGER MODE
Overwrite."
— Set this to a percentage of the total buffer size (for example, 10%, 50%, 75%, and so on). A trigger
TRIGGER POSITION
position of 25% consists of 25% pre- and 75% post-trigger data.
— Always captured in oscillography and can be any FlexLogic parameter (element state, contact input,
TRIGGER SOURCE
virtual output, and so on). The relay sampling rate is 64 samples per cycle.
— Determines the sampling rate at which AC input signals (that is, current and voltage) are stored.
AC INPUT WAVEFORMS
Reducing the sampling rate allows longer records to be stored. This setting has no effect on the internal sampling rate of
the relay, which is always 64 samples per cycle. That is, it has no effect on the fundamental calculations of the device.
When changes are made to the oscillography settings, all existing oscillography records are cleared.
5.3.9.2 Digital channels
SETTINGS  PRODUCT SETUP  OSCILLOGRAPHY  DIGITAL CHANNELS
 DIGITAL CHANNELS
— This setting selects the FlexLogic operand state recorded in an oscillography trace. The length of
DIGITAL 1(63) CHANNEL
each oscillography trace depends in part on the number of parameters selected here. Parameters set to "Off" are ignored.
To populate quickly the rows in the Offline Window, use Ctrl C/V to copy/paste, or click then double-click a row to display a
quick selection window.
D30 LINE DISTANCE PROTECTION SYSTEM – INSTRUCTION MANUAL
Sample rate
Digital
channels
32
32
64
32
32
32
64
32
32
32
64
32
32
32
64
32
32
32
DIGITAL CHANNEL 1:
Off
DIGITAL CHANNEL 63:
Off
Figure 5-49: Quick selection window
Analog
Cycles per
channels
record
16
2399
16
1450
16
666
16
402
16
352
16
213
16
1516
16
851
16
421
TRIGGER MODE
Range: FlexLogic operand
Range: FlexLogic operand
PRODUCT SETUP
is set to "Automatic
5-115
5