Inputs - GE D30 Instruction Manual

Line distance protection system
Hide thumbs Also See for D30:
Table of Contents

Advertisement

SPECIFICATIONS
RMS VOLTAGE
Accuracy:
REAL POWER (WATTS)
Accuracy at 0.1 to 1.5 x CT rating and 0.8 to 1.2 x VT rating:
REACTIVE POWER (VARS)
Accuracy at 0.1 to 1.5 x CT rating and 0.8 to 1.2 x VT rating:
2
APPARENT POWER (VA)
Accuracy at 0.1 to 1.5 x CT rating and 0.8 to 1.2 x VT rating:
FREQUENCY
Accuracy at
V = 0.8 to 1.2 pu:
I = 0.1 to 0.25 pu:
I > 0.25 pu:

2.5.5 Inputs

AC CURRENT
CT rated primary:
CT rated secondary:
Relay burden:
Conversion range:
Standard CT:
Sensitive Ground CT module:
Current withstand:
Short circuit rating:
AC VOLTAGE
VT rated secondary:
VT ratio:
Relay burden:
Conversion range:
Voltage withstand:
FREQUENCY
Nominal frequency setting:
Sampling frequency:
Tracking frequency range:
CONTACT INPUTS
Dry contacts:
Wet contacts:
Selectable thresholds:
Tolerance:
Contacts per common return:
Recognition time:
Debounce time:
Continuous current draw:
2-28
±0.5% of reading from 10 to 208 V
±1.0% of reading at –1.0 ≤ PF < –0.8 and 0.8 < PF ≤ 10
±1.0% of reading at –0.2 ≤ PF ≤ 0.2
±1.0% of reading
±0.001 Hz (when voltage signal is used for frequency measurement)
±0.005 Hz
±0.02 Hz (when current signal is used for frequency measurement)
1 to 50000 A
1 or 5 A by connection
< 0.2 VA at rated secondary
0.02 to 46 × CT rating RMS symmetrical
0.002 to 4.6 × CT rating RMS symmetrical
20 ms at 250 times rated
1 sec at 100 times rated
continuous 4xInom
150000 RMS symmetrical amperes, 250 V maximum (primary current to external CT)
50.0 to 240.0 V
1.00 to 24000.00
< 0.25 VA at 120 V
1 to 275 V
continuous at 260 V to neutral
1 min/hr at 420 V to neutral
25 to 60 Hz
64 samples per power cycle
20 to 70 Hz
1000 Ω maximum
300 V DC maximum
17 V, 33 V, 84 V, 166 V
±10%
4
< 1 ms
0.0 to 16.0 ms in steps of 0.5
4 mA (when energized)
D30 LINE DISTANCE PROTECTION SYSTEM – INSTRUCTION MANUAL